Rated short-circuit breaking capacity (Icu) hits 187 kA at 240 V, drops to 121 kA at 415 V and 440 V, then 75.6 kA at 500 V, and 5.2 kA at 690 V.
Dimensions are 105 mm wide, 181 mm tall, 86 mm deep — a standard 3-pole MCCB footprint for a 200 A frame. Bolts into a panel or mounts on a mounting plate; no DIN-rail clip on this frame size. The 86 mm depth includes the rear arc chamber, so leave clearance behind the panel for the exhaust vents.