Skip to main content
Siemens 3VA2220-5MQ32-0AB0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2220-5MQ32-0AB0 SENTRON MCCB, 200 A, 3-Pole

MPN3VA2220-5MQ32-0AB0

Siemens SENTRON 3VA2220-5MQ32-0AB0, 3-pole molded case circuit breaker, 200 A at 40 °C, adjustable thermal-magnetic trip 40–200 A, 187 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2220-5MQ32-0AB0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.#BEZUG!
Integrated auxiliary / alarm switch ref.3VA9988-0AA11

Ratings

3VA2220-5MQ32-0AB0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C200 A
Current at 45 °C200 A
Current at 50 °C200 A
Current at 55 °C200 A
Current at 60 °C200 A
Current at 65 °C200 A
Current at 70 °C200 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V5.2 kA
Power loss, max.46 W

Protection & Trip Unit

3VA2220-5MQ32-0AB0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU860M
Overcurrent protection functionLSIG
Ground-fault monitoringSummation current formation L-conductor
Grounding protection functionYes

Construction & Connection

3VA2220-5MQ32-0AB0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2220-5MQ32-0AB0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2220-5MQ32-0AB0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2220-5MQ32-0AB0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

What this 200 A MCCB is and what it does

The Siemens 3VA2220-5MQ32-0AB0 is a SENTRON molded case circuit breaker (MCCB) rated 200 A continuous at 40 °C across all three poles, with an adjustable thermal-magnetic trip unit covering 40 A to 200 A full-scale. That means you set the trip threshold to match the load — pump, conveyor, compressor, feeder — without swapping the breaker body. The 3-pole design handles three-phase circuits up to 690 V, with interrupting capacity of 187 kA at 240 V and 121 kA at 415 V, so it safely clears high-fault scenarios common in industrial distribution. Phase failure detection is built in, and the auxiliary switch pack (2 auxiliary switches HP) provides remote status feedback for PLC or SCADA monitoring. Communication function is present — this variant supports integration into higher-level monitoring without an add-on module.

Where it fits in the panel

The breaker measures 105 mm wide, 181 mm tall, and 86 mm deep — a standard MCCB footprint for 200 A class. It mounts directly to a DIN rail or panel plate. The 86 mm depth means it clears most standard enclosure depths without a deep-can modification. Power loss is 46 W maximum at rated load, so factor that into enclosure thermal calculations — especially in a sealed cabinet with other heat sources.

Breaking capacity across voltages

Interrupting ratings step down with voltage: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 5.2 kA at 690 V. The 690 V figure is low enough that you need to verify available fault current at that voltage — typical for 690 V drives or mining gear — before committing the BOM line.

Frequently asked questions

What is the interrupting rating of this MCCB?

At 240 V it interrupts 187 kA; at 415 V and 440 V, 121 kA; at 500 V, 75.6 kA; at 690 V, 5.2 kA.

What is the adjustable trip range?

The thermal-magnetic trip is adjustable from 40 A to 200 A full-scale.

Where can I buy 3VA2220-5MQ32-0AB0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

Does this breaker have communication capability?

Yes, the communication function is present, and it includes phase failure detection and 2 auxiliary switches for remote status.

MPN
3VA2220-5MQ32-0AB0