Siemens 3VA2220-5MQ32-0AE0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2220-5MQ32-0AE0 Circuit Breaker, 55kA @ 415V, 200

MPN3VA2220-5MQ32-0AE0

Siemens 3VA2 IEC frame 250, breaking capacity class M, Icu=55kA @ 415V, 3-pole, motor protection ETU860M, LSIG, In=200A.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Product details

Motor protection breaker, frame 250, 55 kA

The Siemens 3VA2220-5MQ32-0AE0 is a 3-pole IEC motor protection circuit breaker on the 3VA2 platform, frame 250, with a 55 kA Icu at 415 V — breaking capacity class M. That rating means it can safely interrupt a bolted fault up to 55 kA without welding contacts or cascading failure upstream, sized for high-fault industrial distribution where the available short-circuit current is substantial.

ETU860M trip unit — LSIG and adjustable protection

Fitted with the ETU860M electronic trip unit offering LSIG protection: long-time (overload, Ir adjustable 80–200 A), short-time (Isd 1.2–15x In), instantaneous (Ii 3–15x In), and ground-fault (Ig 0.2–1x In, tg 0.05–0.8 s). The In rating is 200 A, so the overload pickup window starts at 80 A and goes to the full 200 A — useful for matching motor FLA on a 200 A frame without stepping down to a smaller breaker. The ground-fault element can be switched off, which is typical on radial feeds where you want GF protection on the feeder but not on every motor branch.

Panel integration and auxiliary switches

This unit includes a nut keeper kit and four auxiliary switches (HQ). The nut keeper secures the breaker on the mounting plate during high-vibration environments — common on motor control center (MCC) bucket assemblies. The four auxiliary switches give status feedback (open/closed, trip) to a PLC or DCS without adding external relays. Mounts on a standard DIN rail or directly to a panel backplate via the frame-250 footprint.

Frequently asked questions

Where can I buy 3VA2220-5MQ32-0AE0 and get a price?

This part is available to order. Submit an RFQ through this listing; availability and current pricing are confirmed at quote time through independent distribution channels.

What is the breaking capacity and trip unit on this breaker?

It has a 55 kA Icu at 415 V (breaking capacity class M) and is fitted with an ETU860M LSIG electronic trip unit, rated In=200 A with adjustable overload (Ir 80–200 A), short-time, instantaneous, and ground-fault protection.

What compliance documentation is available for this breaker?

As a Siemens IEC-frame breaker, it carries IEC 60947-2 certification. RoHS and REACH compliance documentation is typically provided with the shipment; confirm specific documentation requirements at quote time.