Skip to main content
Siemens 3VA2220-7MN32-0HA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2220-7MN32-0HA0 SENTRON MCCB, 200 A, 3-Pole, 330

MPN3VA2220-7MN32-0HA0

Siemens SENTRON 3VA2220-7MN32-0HA0, molded case circuit breaker, 3-pole, 200 A rated, 330 kA breaking capacity at 240 V, motor protection design with shunt trip release.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2220-7MN32-0HA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2220-7MN32-0AA0
3VA2220-7MN32-0HA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C200 A
Current at 45 °C200 A
Current at 50 °C200 A
Current at 55 °C200 A
Current at 60 °C200 A
Current at 65 °C200 A
Current at 70 °C200 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V5.2 kA
Power loss, max.46 W
3VA2220-7MN32-0HA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350M
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2220-7MN32-0HA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2220-7MN32-0HA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2220-7MN32-0HA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2220-7MN32-0HA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The Siemens SENTRON 3VA2220-7MN32-0HA0 is a 3-pole molded case circuit breaker (MCCB) rated for 200 A continuous current across the full 40–70 °C ambient range — no derating needed as the panel warms up. At 415–440 V the interrupting rating is still 242 kA, enough for most industrial low-voltage switchgear; at 690 V it drops to 5.2 kA, which still covers motor branch circuits on 690 V systems. Designed for motor protection, it includes phase failure detection — a critical feature that trips the breaker when one phase drops out, preventing single-phasing damage to a three-phase motor. The adjustable time-delay range of 4–15 s lets you coordinate with downstream motor starters and avoid nuisance trips on inrush. The auxiliary release is a shunt trip (STL), meaning a remote signal — from an E-stop, pressure switch, or PLC output — can electrically trip the breaker. The basic switch supplied is order code 3VA2220-7MN32-0AA0.

As a Siemens SENTRON product, the 3VA2220-7MN32-0HA0 carries IEC/EN 60947-2 certification for molded case circuit breakers. RoHS and REACH compliance documentation is available from the manufacturer. The 330 kA at 240 V rating indicates UL/CSA listing at that level, though the specific certification marks (UL, CSA, CE, UKCA, EAC) should be confirmed on the nameplate or manufacturer's declaration.

Frequently asked questions

Where can I buy the 3VA2220-7MN32-0HA0 and how is it quoted?

This MCCB is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or price is listed here.

What is the breaking capacity of the 3VA2220-7MN32-0HA0 at different voltages?

At 240 V it is 330 kA, at 415 V and 440 V it is 242 kA, at 500 V it is 187 kA, and at 690 V it is 5.2 kA. This covers everything from high-fault 240 V distribution down to 690 V motor circuits.

Will the 3VA2220-7MN32-0HA0 drop into a panel specified around the 3VA1110-5EF32-0LA0?

The 3VA2220-7MN32-0HA0 is a larger frame (200 A rated) compared to the 3VA1110-5EF32-0LA0, which is a 100 A frame. Panel cutouts and bus bar spacing may differ — check the mounting dimensions and terminal centers before assuming a drop-in replacement.

MPN
3VA2220-7MN32-0HA0