Skip to main content
Siemens 3VA2220-7MP32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2220-7MP32-0AA0 SENTRON MCCB, 200 A, 3-pole, moto

MPN3VA2220-7MP32-0AA0
Active

Siemens SENTRON 3VA2220-7MP32-0AA0, molded case circuit breaker, 3-pole, 200 A, motor protection design, adjustable trip class, breaking capacity 330 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2220-7MP32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2220-7MP32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C200 A
Current at 45 °C200 A
Current at 50 °C200 A
Current at 55 °C200 A
Current at 60 °C200 A
Current at 65 °C200 A
Current at 70 °C200 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V5.2 kA
Power loss, max.46 W
3VA2220-7MP32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550M
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2220-7MP32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2220-7MP32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2220-7MP32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2220-7MP32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The Siemens SENTRON 3VA2220-7MP32-0AA0 is a 3-pole molded case circuit breaker (MCCB) rated for 200 A continuous current across the full -25 °C to 70 °C operating range — no derating needed up to 70 °C. It is designed specifically for motor protection, with an adjustable trip class (10A, 10/10E, 20/20E, 30) and a minimum trip time of 3 s, maximum 15 s. The breaking capacity hits 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 5.2 kA at 690 V. That kind of SCCR headroom means it can sit upstream of a motor starter in a high-fault panel without worrying about cascading failures.

The adjustable trip class (10A, 10/10E, 20/20E, 30) lets you match the overload curve to the motor's thermal capacity; a 10E class is tight for a high-inertia load, while 30 gives more time for starting current. Communication function is present, which means it can talk to a PLC or BMS for remote trip indication — no separate shunt trip needed for that.

The 3-pole design with no undervoltage release means it's a straight power path — no extra coil to fail.

Frequently asked questions

What is the breaking capacity of this MCCB at different voltages?

The breaking capacity is 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 5.2 kA at 690 V. That range covers most industrial distribution voltages.

Where can I buy 3VA2220-7MP32-0AA0 and what is the lead time?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

Does this breaker have phase failure detection?

Yes, phase failure detection is included as a standard function, protecting the motor from single-phasing.

MPN
3VA2220-7MP32-0AA0