Skip to main content
Siemens 3VA2225-0HL32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2225-0HL32-0AA0 SENTRON MCCB, 250 A, 440 kA at 41

MPN3VA2225-0HL32-0AA0
Active

Siemens SENTRON 3VA2225-0HL32-0AA0, molded case circuit breaker, 3-pole, 250 A rated continuous current, ETU320 electronic trip unit, 440 kA breaking capacity at 415 V AC, IP40 front protection.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2225-0HL32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2225-0HL32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C241 A
Current at 60 °C232 A
Current at 65 °C222 A
Current at 70 °C213 A
Switching capacity classE
Breaking capacity at 415 V440 kA
Breaking capacity at 690 V187 kA
Power loss, max.48 W
3VA2225-0HL32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2225-0HL32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2225-0HL32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2225-0HL32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2225-0HL32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The 3VA2225-0HL32-0AA0 is a SENTRON 3-pole molded case circuit breaker rated for 250 A continuous current at 40 °C through 50 °C, then derating to 241 A at 55 °C, 232 A at 60 °C, 222 A at 65 °C, and 213 A at 70 °C — so if your panel ambient runs above 50 °C, the breaker's effective capacity drops, and you size the load accordingly.

The IP40 front protection means it's suitable for indoor switchgear but not washdown areas; keep it in a dry, dust-controlled cabinet. Maximum power loss is 48 W — account for that heat in your enclosure's thermal budget, especially when multiple breakers are ganged.

No official successor has been assigned; the 3VA2 platform remains active. For BOM freeze or long-term planning, the ETU320 trip unit and 250 A frame are standard catalog items with broad channel support.

Frequently asked questions

What is the breaking capacity of 3VA2225-0HL32-0AA0 at 415 V?

440 kA at 415 V AC, and 187 kA at 690 V AC. This is suitable for high-fault installations like transformer secondaries or large motor control centers.

What temperature derating applies to this MCCB?

Rated 250 A from 40 °C to 50 °C, then derates to 241 A at 55 °C, 232 A at 60 °C, 222 A at 65 °C, and 213 A at 70 °C. Size your load for the actual panel ambient.

Where can I buy 3VA2225-0HL32-0AA0 and how is it quoted?

Sourced through independent distribution channels. Quoted to order against an RFQ — availability and current pricing confirmed at quote time. No stock count or price is listed here.

Does 3VA2225-0HL32-0AA0 include ground-fault or undervoltage protection?

No. It ships without ground-fault monitoring, without undervoltage release, and without communication functions. It is a line-protection breaker with the ETU320 electronic trip only.

MPN