Siemens 3VA2225-5HL32-0AB0 MCCB, 250A, 3-Pole, 187kA at 240V

MPN3VA2225-5HL32-0AB0

Siemens SENTRON 3VA2225-5HL32-0AB0, molded case circuit breaker, 3-pole, 250 A rated continuous current, 187 kA interrupting capacity at 240 V, line protection design.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2225-5HL32-0AB0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2225-5HL32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA11
3VA2225-5HL32-0AB0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C241 A
Current at 60 °C232 A
Current at 65 °C222 A
Current at 70 °C213 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V4.5 kA
Power loss, max.48 W
3VA2225-5HL32-0AB0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2225-5HL32-0AB0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2225-5HL32-0AB0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA2225-5HL32-0AB0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2225-5HL32-0AB0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The Siemens SENTRON 3VA2225-5HL32-0AB0 is a 3-pole molded case circuit breaker rated for 250 A continuous current at 40 °C, with no derating needed up to 50 °C — above that, it drops to 241 A at 55 °C and 213 A at 70 °C, so panel ambient temperature directly governs the usable ampacity. Interrupting capacity is 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 4.5 kA at 690 V — these are the SCCR values that determine whether this breaker can clear a fault without upstream coordination failure.

Maximum power loss is 48 W, which contributes to the enclosure's thermal budget and must be factored into the panel cooling calculation.