Skip to main content
Siemens 3VA2225-5HL32-0CH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2225-5HL32-0CH0 SENTRON MCCB, 250 A, 3-Pole

MPN3VA2225-5HL32-0CH0

Siemens SENTRON 3VA2225-5HL32-0CH0, molded case circuit breaker, 3-pole, 250 A, line protection, with undervoltage release and auxiliary switches.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2225-5HL32-0CH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2225-5HL32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA2225-5HL32-0CH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C241 A
Current at 60 °C232 A
Current at 65 °C222 A
Current at 70 °C213 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V4.5 kA
Power loss, max.50.5 W

Protection & Trip Unit

3VA2225-5HL32-0CH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2225-5HL32-0CH0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2225-5HL32-0CH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA2225-5HL32-0CH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2225-5HL32-0CH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

Siemens SENTRON 3VA2225-5HL32-0CH0 — 250 A MCCB for Line Protection

The Siemens SENTRON 3VA2225-5HL32-0CH0 is a 3-pole molded case circuit breaker (MCCB) rated for 250 A continuous current, designed for line protection in distribution panels. It carries a maximum interrupting capacity of 187 kA at 240 V and 121 kA at 415 V and 440 V, dropping to 75.6 kA at 500 V and 4.5 kA at 690 V — the voltage-dependent curve you need to check against your available fault current at the panelboard.

Thermal Derating and Panel Fit

The 250 A rating holds at ambient temperatures up to 50 °C. Above that, it derates linearly: 241 A at 55 °C, 232 A at 60 °C, 222 A at 65 °C, and 213 A at 70 °C. If your panel runs hot — near a furnace line or in a sealed enclosure — size the load accordingly or plan for forced ventilation. Dimensions are 105 mm wide, 181 mm high, and 86 mm deep. The 105 mm width is standard for a 3-pole MCCB in this class — it fits a typical 200 mm DIN-rail spacing with room for side-by-side auxiliary modules. The 86 mm depth leaves clearance for rear-connected busbars in a standard 400 mm deep enclosure. Operating temperature range is -25 °C to 70 °C; storage range is -40 °C to 80 °C. The storage limit governs handling and warehousing, not running conditions.

Auxiliary and Release Configuration

This variant ships with an undervoltage release (UVR) and a complement of 2 auxiliary switches plus 1 trip alarm switch (HQ type). The UVR trips the breaker when control voltage drops below a threshold — useful for safety circuits that need to drop power on loss of control supply. The auxiliary switches provide status feedback to a PLC or indicator lamp; the trip alarm switch signals a fault condition separately from a manual open. A trip indicator is present on the front face, giving a visual flag when the breaker has tripped on overcurrent or short circuit — no need to probe with a meter to distinguish a trip from a manual OFF. The basic switch (the interrupting core) carries order code 3VA2225-5HL32-0AA0, which is the base breaker without auxiliaries. This variant adds the UVR and switch package on top of that core.

Sourcing and Availability

Maximum power loss at rated current is 50.5 W — factor that into your enclosure thermal budget if the breaker is in a sealed cabinet with other heat sources.

Frequently asked questions

Where can I buy 3VA2225-5HL32-0CH0 and get a price?

This part is sourced to order against an RFQ through our independent distribution network. Submit an RFQ for current pricing and availability confirmation.

What is the interrupting capacity of 3VA2225-5HL32-0CH0 at different voltages?

The interrupting capacity is voltage-dependent: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 4.5 kA at 690 V. Verify your available fault current at the panel voltage before specifying.

Does 3VA2225-5HL32-0CH0 include an undervoltage release?

Yes, this variant includes an undervoltage release (UVR) plus 2 auxiliary switches and 1 trip alarm switch (HQ type).

MPN
3VA2225-5HL32-0CH0