Skip to main content
Siemens 3VA2225-5HL32-0DL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2225-5HL32-0DL0 SENTRON MCCB, 250 A, 3-Pole, ETU3

MPN3VA2225-5HL32-0DL0

Siemens SENTRON 3VA2225-5HL32-0DL0, molded case circuit breaker, 3-pole, 250 A, line protection, ETU320 overcurrent release, 187 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2225-5HL32-0DL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2225-5HL32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22

Ratings

3VA2225-5HL32-0DL0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C241 A
Current at 60 °C232 A
Current at 65 °C222 A
Current at 70 °C213 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V79 kA
Breaking capacity at 690 V5.1 kA
Power loss, max.50.5 W

Protection & Trip Unit

3VA2225-5HL32-0DL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320

Construction & Connection

3VA2225-5HL32-0DL0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2225-5HL32-0DL0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4

Environmental

3VA2225-5HL32-0DL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2225-5HL32-0DL0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

Line protection MCCB for the panel schedule

The Siemens 3VA2225-5HL32-0DL0 is a SENTRON molded case circuit breaker rated for 250 A continuous current (Iu) across a 3-pole configuration, carrying an ETU320 electronic overcurrent release for line protection duty. Its interrupting capacity hits 187 kA at 240 V and 121 kA at 415/440 V, dropping to 79 kA at 500 V and 5.1 kA at 690 V — the SCCR headroom you need for high-fault panel coordination without cascading upstream. Thermal derating is published from 40 °C through 70 °C: the breaker holds 250 A up to 50 °C, then steps down to 241 A at 55 °C, 232 A at 60 °C, 222 A at 65 °C, and 213 A at 70 °C. That curve governs the actual ampacity in a crowded enclosure.

Auxiliary and release configuration

The breaker ships with an undervoltage release (UVR) and a 2+1+1 auxiliary contact block: two auxiliary switches, one trip alarm switch, and one electrical alarm switch (HQ type). That covers remote status and shunt-trip supervision without adding a separate accessory module. The basic switch is order code 3VA2225-5HL32-0AA0; the integrated auxiliary trip is 3VA9608-0BB25. Both are factory-fitted, not field-add — verify the nameplate matches the BOM before panel build.

Physical fit and environmental limits

Dimensions are 105 mm wide, 181 mm tall, and 86 mm deep — a standard 3-pole MCCB footprint for DIN-rail or panel-mount integration. Operating temperature range is -25 °C to 70 °C; storage range is -40 °C to 80 °C. Maximum power loss is 50.5 W at rated current — factor that into enclosure thermal calculations if the panel is sealed or has limited convection.

Frequently asked questions

What trip unit does the 3VA2225-5HL32-0DL0 use?

It uses the ETU320 electronic overcurrent release, configured for line protection (not ground fault or communication). No voltage-trip or phase-failure detection is integrated.

Will 3VA2225-5HL32-0DL0 drop into a panel specified for 3VA1112-5EF32-0CA0?

Both are 3-pole SENTRON MCCBs, but the 3VA2225 is a larger frame rated 250 A versus the 3VA1112 frame's lower current. Panel cutout and bus-bar spacing differ between frame sizes — verify the mounting footprint and lug dimensions against your existing bus work before assuming a direct swap.

MPN
3VA2225-5HL32-0DL0