Skip to main content
Siemens 3VA2225-5HL42-0AE0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2225-5HL42-0AE0 SENTRON MCCB, 250 A, 4-Pole, 187

MPN3VA2225-5HL42-0AE0

Siemens SENTRON 3VA2225-5HL42-0AE0, molded case circuit breaker, 4-pole, 250 A continuous, 187 kA interrupting at 240 V, line protection design.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2225-5HL42-0AE0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2225-5HL42-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA2225-5HL42-0AE0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C241 A
Current at 60 °C232 A
Current at 65 °C222 A
Current at 70 °C213 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V4.5 kA
Power loss, max.48 W

Protection & Trip Unit

3VA2225-5HL42-0AE0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2225-5HL42-0AE0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2225-5HL42-0AE0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4

Environmental

3VA2225-5HL42-0AE0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2225-5HL42-0AE0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.13 in
Width (in)5.51 in
Depth (in)3.39 in

Product details

SENTRON 3VA2225-5HL42-0AE0 — 250 A MCCB for Line Protection

The Siemens SENTRON 3VA2225-5HL42-0AE0 is a 4-pole molded case circuit breaker (MCCB) rated for 250 A continuous at 40 °C, designed for line protection in distribution panels. It carries a 187 kA interrupting capacity at 240 V — enough to handle high-fault utility feeds without cascading upstream. At 415 V and 440 V it still breaks 121 kA, dropping to 75.6 kA at 500 V and 4.5 kA at 690 V, so the SCCR headroom depends on your system voltage. The 250 A rating holds flat from 40 °C through 50 °C, then derates to 241 A at 55 °C, 232 A at 60 °C, 222 A at 65 °C, and 213 A at 70 °C. That means in a warm enclosure — say 55 °C ambient — you lose 9 A of headroom, still within the margin for most 200 A feeders. Maximum power loss is 48 W, so the heat load on the panel is modest for a 250 A frame.

Panel Fit and Mounting

The 3VA2225-5HL42-0AE0 measures 86 mm deep, 140 mm wide, and 181 mm high. The 140 mm width on a 4-pole MCCB is standard for the SENTRON 3VA2 frame — it occupies the same footprint as other 4-pole units in the series, so a panel laid out for a 3VA1 or 3VA2 4-pole breaker will accept this drop-in. Depth of 86 mm (3.39 in) means it clears most 200 mm deep enclosures with room for rear-connected busbars.

Lifecycle and Sourcing

The basic switch variant is 3VA2225-5HL42-0AA0; the -0AE0 adds 4 auxiliary switches HQ. If you are replacing a -0AA0 and need the aux contacts, this is the direct upgrade. No rewiring of the line or load terminals — same frame, same mounting hole pattern.

Frequently asked questions

Where can I buy 3VA2225-5HL42-0AE0 and get a price?

Sourced and quoted to order against an RFQ through our industrial automation desk. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm number.

What is the interrupting capacity at 240 V?

187 kA at 240 V. At 415 V and 440 V it is 121 kA; at 500 V it drops to 75.6 kA; at 690 V it is 4.5 kA.

Will 3VA2225-5HL42-0AE0 drop into a panel specified for 3VA1110-5EF32-0AM0?

The 3VA2 frame is physically larger than the 3VA1 frame — the 3VA1110 is a 3-pole 100 A frame. The 3VA2225 is 4-pole 250 A with wider dimensions. It will not drop into a panel cutout or busbar layout designed for the 3VA1 series without mechanical modification.

MPN
3VA2225-5HL42-0AE0