Skip to main content
Siemens 3VA2225-5HL42-0BH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2225-5HL42-0BH0 SENTRON MCCB, 250 A, 4-Pole, Line

MPN3VA2225-5HL42-0BH0

Siemens SENTRON series, Molded case circuit breaker, 3VA2225-5HL42-0BH0, 250 A continuous at 40°C, 4-pole, line protection design, undervoltage release fitted, 86 mm depth.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2225-5HL42-0BH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2225-5HL42-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA2225-5HL42-0BH0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C241 A
Current at 60 °C232 A
Current at 65 °C222 A
Current at 70 °C213 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V4.5 kA
Power loss, max.50.5 W
3VA2225-5HL42-0BH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2225-5HL42-0BH0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2225-5HL42-0BH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA2225-5HL42-0BH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2225-5HL42-0BH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.13 in
Width (in)5.51 in
Depth (in)3.39 in

Product details

The Siemens SENTRON 3VA2225-5HL42-0BH0 is a 4-pole molded case circuit breaker rated 250 A continuous at 40 °C, designed for line protection in distribution panels.

Short-circuit ratings that define the coordination study

The interrupting capacity varies sharply with system voltage: 187 kA at 240 V, 121 kA at 415 V or 440 V, 75.6 kA at 500 V, and 4.5 kA at 690 V. That 690 V figure is the one that catches people — if your transformer secondary is 690 V line-to-line, this breaker still clears a fault, but the available fault current at that voltage must stay under 4.5 kA. On a 480 V panel with a typical 65 kA SCCR requirement, the 75.6 kA rating at 500 V gives comfortable headroom.

The breaker holds 250 A continuously from 40 °C through 50 °C. Above that it derates: 241 A at 55 °C, 232 A at 60 °C, 222 A at 65 °C, 213 A at 70 °C. If this breaker lives in a non-air-conditioned enclosure near a furnace line or transformer, size the load at the 55 °C or 60 °C figure, not the 40 °C nameplate. Mounting dimensions are 181 mm tall, 140 mm wide, 86 mm deep — fits standard SENTRON 4-pole cutouts in a distribution panel.

Frequently asked questions

Where can I buy 3VA2225-5HL42-0BH0 and get a price?

Sourced and quoted to order against an RFQ through independent distribution. Submit a request for current pricing and availability.

What are the short-circuit ratings at common voltages?

187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 4.5 kA at 690 V.

What is the continuous current rating and how does it derate with temperature?

250 A continuous from 40 °C to 50 °C, then derates to 241 A at 55 °C, 232 A at 60 °C, 222 A at 65 °C, and 213 A at 70 °C.

MPN