Skip to main content
Siemens 3VA2225-5HL42-0JC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2225-5HL42-0JC0 SENTRON MCCB, 250 A, 4-Pole, Line

MPN3VA2225-5HL42-0JC0

Siemens SENTRON 3VA2, molded case circuit breaker (MCCB), 4-pole, 250 A rated continuous current, line protection version with ETU320 electronic trip unit, shunt trip (STL), 2 auxiliary switches HQ, breaking capacity 187 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2225-5HL42-0JC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2225-5HL42-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA2225-5HL42-0JC0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C241 A
Current at 60 °C232 A
Current at 65 °C222 A
Current at 70 °C213 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V79 kA
Breaking capacity at 690 V5.1 kA
Power loss, max.48 W

Protection & Trip Unit

3VA2225-5HL42-0JC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320

Construction & Connection

3VA2225-5HL42-0JC0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2225-5HL42-0JC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2225-5HL42-0JC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2225-5HL42-0JC0 — Mechanical
ParameterValue
Height181 mm
Width140 mm
Depth86 mm

Product details

What this MCCB carries and what it means for your panel

The Siemens 3VA2225-5HL42-0JC0 is a SENTRON molded case circuit breaker (MCCB) rated for 250 A continuous current (Iu) across a 4-pole configuration. The ETU320 electronic trip unit gives you adjustable overload and short-circuit protection curves — line protection version, so it's set up for feeder and distribution duty, not motor starting. Breaking capacity hits 187 kA at 240 V and 121 kA at 415 V, which means it can interrupt high-fault-current faults without upstream coordination headaches in most industrial distribution panels.

Thermal derating — the real continuous current in a warm cabinet

Rated 250 A at 40 °C, 45 °C, and 50 °C. At 55 °C it derates to 241 A, at 60 °C to 232 A, at 65 °C to 222 A, and at 70 °C to 213 A. If your panel ambient runs above 50 °C — common in a packed enclosure or near a dryer section — plan on that 213 A ceiling at 70 °C. The maximum operating temperature is 70 °C; storage range is -40 °C to 80 °C.

Built-in auxiliary and shunt trip — what comes inside

Factory-fitted with 2 auxiliary switches (HQ type) and a shunt trip (STL) release. The shunt trip allows remote tripping via a control voltage — useful for emergency-stop circuits or interlocking. The basic switch assembly is order code 3VA2225-5HL42-0AA0; the integrated auxiliary trip module is 3VA9688-0BL32. No undervoltage release, no ground-fault monitoring, no communication module on this variant.

Physical fit — DIN-rail or panel-mount dimensions

Width 140 mm, height 181 mm, depth 86 mm. That 140 mm width is the standard 4-pole MCCB footprint for this SENTRON frame size.

Frequently asked questions

What is the depth of 3VA2225-5HL42-0JC0?

Depth is 86 mm. Width 140 mm, height 181 mm.

MPN
3VA2225-5HL42-0JC0