Breaking capacity runs 187 kA at 240 V, 121 kA at 415 V and 440 V, 79 kA at 500 V, and 5.1 kA at 690 V, so it handles high-fault industrial distribution panels without cascading upstream.
At 55 °C it's 241 A, at 60 °C it's 232 A, at 65 °C it's 222 A, and at 70 °C it's 213 A. The IP40 front protection keeps dust and small tools out of the mechanism; the body dimensions (181 mm height, 105 mm width, 86 mm depth) fit standard SENTRON 3VA panel cutouts and busbar systems.