Skip to main content
Siemens 3VA2225-5HN32-0AC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2225-5HN32-0AC0 SENTRON MCCB, 250 A, 3-Pole, ETU3

MPN3VA2225-5HN32-0AC0

Siemens SENTRON 3VA2225-5HN32-0AC0, molded case circuit breaker, 3-pole, 250 A rated continuous current, ETU350 electronic trip unit, line protection version, breaking capacity 187 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2225-5HN32-0AC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2225-5HN32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA2225-5HN32-0AC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C241 A
Current at 60 °C232 A
Current at 65 °C222 A
Current at 70 °C213 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V79 kA
Breaking capacity at 690 V5.1 kA
Power loss, max.48 W
3VA2225-5HN32-0AC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
3VA2225-5HN32-0AC0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2225-5HN32-0AC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA2225-5HN32-0AC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2225-5HN32-0AC0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

Breaking capacity runs 187 kA at 240 V, 121 kA at 415 V and 440 V, 79 kA at 500 V, and 5.1 kA at 690 V, so it handles high-fault industrial distribution panels without cascading upstream.

At 55 °C it's 241 A, at 60 °C it's 232 A, at 65 °C it's 222 A, and at 70 °C it's 213 A. The IP40 front protection keeps dust and small tools out of the mechanism; the body dimensions (181 mm height, 105 mm width, 86 mm depth) fit standard SENTRON 3VA panel cutouts and busbar systems.

Frequently asked questions

What is the breaking capacity of 3VA2225-5HN32-0AC0 at different voltages?

Breaking capacity is 187 kA at 240 V, 121 kA at 415 V and 440 V, 79 kA at 500 V, and 5.1 kA at 690 V.

What trip unit does 3VA2225-5HN32-0AC0 use?

It uses the ETU350 electronic trip unit, configured for line protection without undervoltage release or communication functions.

How do I get current pricing and availability for 3VA2225-5HN32-0AC0?

Submit an RFQ through this listing. The part is sourced to order through independent distribution; current pricing and stock levels are confirmed at quote time.

MPN
3VA2225-5HN32-0AC0