The Siemens SENTRON 3VA2225-5HN32-0JA0 is a 3-pole molded case circuit breaker rated for 250 A continuous current. It delivers 187 kA interrupting capacity at 240 V and 121 kA at 415/440 V, with a derated 75.6 kA at 500 V and 4.5 kA at 690 V — covering the full low-voltage distribution range from 240 V line-to-line up to 690 V phase-to-phase. The 250 A frame holds its full rating up to 50 °C ambient; above that, derate linearly to 213 A at 70 °C (the maximum operating temperature). Designed for line protection, this MCCB carries a shunt trip release (STL) for remote tripping — no undervoltage release, no ground-fault monitoring, and no auxiliary switch fitted on this variant. The basic switch core is order code 3VA2225-5HN32-0AA0.

Siemens 3VA2225-5HN32-0JA0 SENTRON MCCB, 250A, 3-Pole, 187kA
MPN3VA2225-5HN32-0JA0
Siemens SENTRON 3VA2225-5HN32-0JA0, molded case circuit breaker, 3-pole, 250 A rated continuous current, 187 kA interrupting at 240 V, line protection design, with shunt trip release.
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026
Specifications
Identification
| Parameter | Value |
|---|---|
| Product designation | Molded case circuit breaker |
| Brand / range | SENTRON |
| Basic switch (supplied) ref. | 3VA2225-5HN32-0AA0 |
Ratings
| Parameter | Value |
|---|---|
| Number of poles | 3 |
| Rated operational voltage Ue (AC) | 690 V |
| Rated insulation voltage Ui | 800 V |
| Current at 40 °C | 250 A |
| Current at 45 °C | 250 A |
| Current at 50 °C | 250 A |
| Current at 55 °C | 241 A |
| Current at 60 °C | 232 A |
| Current at 65 °C | 222 A |
| Current at 70 °C | 213 A |
| Switching capacity class | M |
| Breaking capacity at 240 V | 187 kA |
| Breaking capacity at 415 V | 121 kA |
| Breaking capacity at 440 V | 121 kA |
| Breaking capacity at 500 V | 75.6 kA |
| Breaking capacity at 690 V | 4.5 kA |
| Power loss, max. | 48 W |
Protection & Trip Unit
| Parameter | Value |
|---|---|
| Overcurrent release (trip unit) type | ETU350 |
| Overcurrent protection function | LSI |
| Ground-fault monitoring | Without |
| Grounding protection function | No |
Construction & Connection
| Parameter | Value |
|---|---|
| Main circuit connection type | on both sides nut keeper kit |
| Main circuit connector arrangement | Front terminal |
| Protection class (IP), front | IP40 |
Accessories & Functions
| Parameter | Value |
|---|---|
| Undervoltage release | No |
| Voltage trigger | Yes |
| Trip indicator | No |
| Communication function | No |
| Measurement function | No |
| Motor drive option | Yes |
| Auxiliary CO contacts | 0 |
Environmental
| Parameter | Value |
|---|---|
| Operating temperature, max. | 70 °C |
| Operating temperature, min. | -25 °C |
| Storage temperature, max. | 80 °C |
| Storage temperature, min. | -40 °C |
Mechanical
| Parameter | Value |
|---|---|
| Mechanical service life (operating cycles), typ. | 25 000 |
| Height | 181 mm |
| Width | 105 mm |
| Depth | 86 mm |
| Height (in) | 7.13 in |
| Width (in) | 4.13 in |
| Depth (in) | 3.39 in |
Product details
Frequently asked questions
What are the interrupting ratings of 3VA2225-5HN32-0JA0 at different voltages?
187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 4.5 kA at 690 V.
What is the continuous current rating and thermal derating for 3VA2225-5HN32-0JA0?
Rated 250 A continuous up to 50 °C ambient. Derates to 241 A at 55 °C, 232 A at 60 °C, 222 A at 65 °C, and 213 A at 70 °C.
Where can I buy 3VA2225-5HN32-0JA0 and how is it quoted?
Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for volume pricing.
MPN
3VA2225-5HN32-0JA0