Its interrupting capacity scales with system voltage: 187 kA at 240 V AC, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 4.5 kA at 690 V — so at typical 480 V industrial feeds it still holds a very high 75.6 kA, giving plenty of headroom for high-fault panels.
Above that it derates linearly: 241 A at 55 °C, 232 A at 60 °C, 222 A at 65 °C, and 213 A at 70 °C.
It does not include an undervoltage release or ground-fault monitoring module; the only auxiliary release is the shunt trip. If you need UVR or GF protection, you will add external modules or choose a different variant.