Siemens 3VA2225-5HN32-0KC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2225-5HN32-0KC0 SENTRON MCCB, 250 A, 3-Pole, 187

MPN3VA2225-5HN32-0KC0

Siemens SENTRON 3VA2225-5HN32-0KC0, molded case circuit breaker, 3-pole, 250 A, 187 kA at 240 V, line protection, ETU350 release, shunt trip.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2225-5HN32-0KC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2225-5HN32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA2225-5HN32-0KC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C241 A
Current at 60 °C232 A
Current at 65 °C222 A
Current at 70 °C213 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V79 kA
Breaking capacity at 690 V5.1 kA
Power loss, max.48 W

Protection & Trip Unit

3VA2225-5HN32-0KC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350

Construction & Connection

3VA2225-5HN32-0KC0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2225-5HN32-0KC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2225-5HN32-0KC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2225-5HN32-0KC0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

MCCB for high-fault panels

The Siemens SENTRON 3VA2225-5HN32-0KC0 is a 3-pole molded case circuit breaker rated for 250 A continuous current, with a maximum power loss of 48 W. It carries an interrupting capacity of 187 kA at 240 V, dropping to 121 kA at 415 V and 440 V, then 79 kA at 500 V, and 5.1 kA at 690 V — so it handles high available fault current at typical distribution voltages without needing an upstream current-limiting fuse. Rated insulation voltage is 800 V, and the breaker is configured for line protection with an ETU350 electronic trip unit. It includes a shunt trip (STL) auxiliary release and two auxiliary switches (HQ version). No undervoltage release, no ground-fault monitoring, no communication function, and no phase-failure detection — this is a straightforward thermal-magnetic-plus-electronic trip breaker for main feeder or large branch protection.

Thermal derating and endurance

The breaker holds its full 250 A rating from 40 °C up to 50 °C ambient. Above that it derates: 241 A at 55 °C, 232 A at 60 °C, 222 A at 65 °C, and 213 A at 70 °C. Mechanical endurance is 20 000 operations — that's the latching endurance, not the electrical endurance under load. For a main breaker seeing a few cycles per day, that's a decade-plus of service. Operating temperature range is -25 °C to 70 °C; storage range is -40 °C to 80 °C. No trip indicator on the front, so you'll need the auxiliary switch contacts to signal status back to a PLC or annunciator panel.

Panel fit and integration

Dimensions are 105 mm wide, 181 mm high, and 86 mm deep — fits a standard Siemens 3VA mounting footprint. The basic switch assembly carries order code 3VA2225-5HN32-0AA0; the integrated auxiliary trip is 3VA9688-0BL33. No communication module, so it's a standalone breaker for hardwired control circuits.

Frequently asked questions

Where can I buy 3VA2225-5HN32-0KC0?

It's sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the interrupting capacity of this breaker?

187 kA at 240 V, 121 kA at 415 V and 440 V, 79 kA at 500 V, and 5.1 kA at 690 V.

Does this breaker include a shunt trip?

Yes, it has a shunt trip (STL) auxiliary release and two auxiliary switches (HQ version). No undervoltage release, no ground-fault monitoring.

MPN
3VA2225-5HN32-0KC0