Siemens SENTRON 3VA2225-5HN32-0KH0 — 250 A MCCB for Line Protection
Above that, derating is linear: 241 A at 55 °C, 232 A at 60 °C, 222 A at 65 °C, and 213 A at 70 °C.
Interrupting Capacity by Voltage Level
Interrupting capacity drops with system voltage: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 4.5 kA at 690 V. The 690 V figure is notably lower — verify available fault current if applying on a 690 V line; this breaker is not intended for high-fault 690 V main service.
Integrated Auxiliary and Trip Functions
No undervoltage release is included. The trip indicator and voltage trigger are present, giving visual and electrical status feedback for PLC or SCADA monitoring.