Skip to main content
Siemens 3VA2225-5HN42-0HH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2225-5HN42-0HH0 SENTRON MCCB, 250 A, 4-Pole, 187

MPN3VA2225-5HN42-0HH0

Siemens SENTRON 3VA2 series, molded case circuit breaker (MCCB), 3VA2225-5HN42-0HH0, 4-pole, 250 A rated, 187 kA breaking capacity at 240 VAC, line protection design.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2225-5HN42-0HH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2225-5HN42-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA2225-5HN42-0HH0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C241 A
Current at 60 °C232 A
Current at 65 °C222 A
Current at 70 °C213 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V4.5 kA
Power loss, max.48 W
3VA2225-5HN42-0HH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2225-5HN42-0HH0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2225-5HN42-0HH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA2225-5HN42-0HH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2225-5HN42-0HH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.13 in
Width (in)5.51 in
Depth (in)3.39 in

Product details

Siemens 3VA2225-5HN42-0HH0 — 250 A SENTRON MCCB, 4-Pole, Line Protection

The Siemens 3VA2225-5HN42-0HH0 is a SENTRON molded case circuit breaker (MCCB) rated for 250 A continuous current at 40 °C, with a 4-pole configuration and a maximum breaking capacity of 187 kA at 240 VAC.

At 240 VAC the 3VA2225-5HN42-0HH0 interrupts 187 kA; at 415 VAC that figure is 121 kA, and at 690 VAC it drops to 4.5 kA. The 2500 A Icu rating at 2500 A rated current means this breaker is sized for high-fault installations where a standard 65 kA MCCB would not hold coordination.

The breaker carries 250 A continuously from 40 °C through 50 °C ambient; above that it derates linearly to 213 A at 70 °C.

Frequently asked questions

Where can I buy 3VA2225-5HN42-0HH0 and get a price?

This part is sourced to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to confirm current availability and pricing — no stock or price figures are published here.

What is the breaking capacity of 3VA2225-5HN42-0HH0 at 480 VAC?

The published breaking capacity at 500 VAC is 75.6 kA, which is the closest published point for a 480 VAC system. At 415 VAC it is 121 kA, and at 690 VAC it drops to 4.5 kA.

Does 3VA2225-5HN42-0HH0 include a shunt trip or undervoltage release?

It includes a shunt trip (STL) as the auxiliary release. It does not include an undervoltage release. The auxiliary switch configuration is 2 auxiliary switches plus 1 trip alarm switch (HQ).

MPN
3VA2225-5HN42-0HH0