Skip to main content
Siemens 3VA2225-5HN42-0KA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2225-5HN42-0KA0 SENTRON MCCB, 250 A, 4-Pole, ETU3

MPN3VA2225-5HN42-0KA0

Siemens SENTRON 3VA2, molded case circuit breaker, 4-pole, 250 A, ETU350 electronic trip unit, shunt trip release, 187 kA interrupting at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2225-5HN42-0KA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2225-5HN42-0AA0

Ratings

3VA2225-5HN42-0KA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C241 A
Current at 60 °C232 A
Current at 65 °C222 A
Current at 70 °C213 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V79 kA
Breaking capacity at 690 V5.1 kA
Power loss, max.48 W

Protection & Trip Unit

3VA2225-5HN42-0KA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350

Construction & Connection

3VA2225-5HN42-0KA0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2225-5HN42-0KA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2225-5HN42-0KA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2225-5HN42-0KA0 — Mechanical
ParameterValue
Height181 mm
Width140 mm
Depth86 mm

Product details

Siemens 3VA2225-5HN42-0KA0 — 250 A SENTRON MCCB with ETU350 Trip Unit

The Siemens 3VA2225-5HN42-0KA0 is a SENTRON molded case circuit breaker rated for 250 A continuous current (Iu) across a 4-pole frame, fitted with an ETU350 electronic overcurrent release and a factory-integrated shunt trip (STL). Interrupting capacity reaches 187 kA at 240 V AC, 121 kA at 415/440 V, and 79 kA at 500 V — high enough to handle most industrial fault-current scenarios without cascading upstream breakers. The ETU350 release provides adjustable long-time, short-time, instantaneous, and ground-fault protection curves, making this breaker suitable for feeder and main-switch duty in distribution panels.

Current Ratings and Thermal Derating

The 250 A rating holds flat from 40 °C through 50 °C ambient; above that it derates to 241 A at 55 °C, 232 A at 60 °C, 222 A at 65 °C, and 213 A at 70 °C. Maximum power dissipation is 48 W at full load — relevant for enclosure thermal calculations when grouping multiple breakers. Operating temperature range spans -25 °C to +70 °C; storage range extends from -40 °C to +80 °C.

Frame Dimensions and Panel Fit

The breaker measures 181 mm high × 140 mm wide × 86 mm deep — a standard 4-pole MCCB footprint that fits Siemens 3VA switchboard and distribution panel cutouts. Rated insulation voltage is 800 V, so the breaker can be applied in 690 V systems with adequate clearance.

Frequently asked questions

What trip unit does this MCCB use?

It uses the ETU350 electronic overcurrent release with adjustable long-time, short-time, instantaneous, and ground-fault protection curves.

MPN
3VA2225-5HN42-0KA0