Skip to main content
Siemens 3VA2225-5JQ32-0BH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2225-5JQ32-0BH0 SENTRON MCCB, 250 A, 3-Pole

MPN3VA2225-5JQ32-0BH0

Siemens SENTRON 3VA2225-5JQ32-0BH0, molded case circuit breaker, 3-pole, 250 A (at 40 °C), line protection, with undervoltage release and communication function.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2225-5JQ32-0BH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2225-5JQ32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA2225-5JQ32-0BH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C238 A
Current at 60 °C225 A
Current at 65 °C213 A
Current at 70 °C200 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V4.5 kA
Power loss, max.50.5 W
3VA2225-5JQ32-0BH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU560
Overcurrent protection functionLSIG
Ground-fault monitoringSummation current formation L-conductor
Grounding protection functionYes
3VA2225-5JQ32-0BH0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2225-5JQ32-0BH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA2225-5JQ32-0BH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2225-5JQ32-0BH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The Siemens SENTRON 3VA2225-5JQ32-0BH0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection, carrying 250 A continuously at 40 °C and derating to 200 A at 70 °C. It breaks up to 187 kA at 240 V, 121 kA at 415/440 V, and holds a 4.5 kA rating at 690 V — so the interrupting capacity scales with your system voltage, not a single headline number.

Above that, the thermal curve pulls back: 238 A at 55 °C, 225 A at 60 °C, 213 A at 65 °C, 200 A at 70 °C. That derating matters for coordination studies. The adjustable thermal-magnetic trip (initial value 50 A, full-scale 250 A) lets you set the overload threshold within that range, so one breaker frame covers a spread of load sizes. The trip indicator confirms the breaker opened on fault, not manual operation. Breaking capacity: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, 4.5 kA at 690 V. For a 480 V system (common in North America), the relevant figure is the 500 V row at 75.6 kA — that's the SCCR the breaker can interrupt without welding or rupturing. At 690 V the capacity drops sharply to 4.5 kA, so it's not a universal high-voltage breaker; it's sized for distribution up to 500 V.

Auxiliaries and integration

The auxiliary switches report position (open/closed/tripped) to a PLC or status lamp. Communication function is built in, so it can talk to a higher-level system via the SENTRON communication modules or PROFIBUS/PROFINET gateway for remote monitoring and trip-event logging.

Physical fit and panel considerations

Dimensions: 181 mm high, 105 mm wide, 86 mm deep (7.13 x 4.13 x 3.39 in). No need to re-drill the panel if you're swapping between 3VA2 variants of the same frame. The storage range is wider because the breaker isn't dissipating heat when stored — that's the handling limit, not the running limit.

This is a current-production part from Siemens, part of the SENTRON 3VA family.

Frequently asked questions

What auxiliaries are included with 3VA2225-5JQ32-0BH0?

It includes an undervoltage release (UVR), two auxiliary switches, and one trip alarm switch (HQ configuration).

MPN
3VA2225-5JQ32-0BH0