Skip to main content
Siemens 3VA2225-5KP32-0DC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2225-5KP32-0DC0 SENTRON MCCB, 250A, 3-Pole, 187kA

MPN3VA2225-5KP32-0DC0

Siemens SENTRON 3VA2225-5KP32-0DC0, molded case circuit breaker, 3-pole, 250 A continuous at 40 °C, interrupting capacity 187 kA at 240 V, line protection design with undervoltage release and communication function.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2225-5KP32-0DC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2225-5KP32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA2225-5KP32-0DC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C238 A
Current at 60 °C225 A
Current at 65 °C213 A
Current at 70 °C200 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V4.5 kA
Power loss, max.50.5 W
3VA2225-5KP32-0DC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU850
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2225-5KP32-0DC0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2225-5KP32-0DC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts2
3VA2225-5KP32-0DC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2225-5KP32-0DC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The Siemens SENTRON 3VA2225-5KP32-0DC0 is a 3-pole molded case circuit breaker rated for 250 A continuous current at 40 °C ambient, with a trip range of 375 A minimum to 2 500 A maximum. It is designed for line protection and includes an undervoltage release and a communication function. The interrupting capacity is 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 4.5 kA at 690 V. This is a current-production part, so the failure mode to plan for is not obsolescence but correct coordination with downstream devices to avoid nuisance trips or cascade faults.

Above that, derate linearly: 238 A at 55 °C, 225 A at 60 °C, 213 A at 65 °C, and 200 A at 70 °C. If your panel internal temperature runs at 55 °C, the breaker's effective continuous current is 238 A — not the nameplate 250 A. That 12 A delta matters when sizing for a non-linear load profile near the top of the trip curve.

Interrupting capacity by voltage level

At 415 V and 440 V it holds 121 kA, dropping to 75.6 kA at 500 V and 4.5 kA at 690 V. For a 480 V panel, the available fault current must be below 75.6 kA to use this breaker without series rating restrictions. That is the number to verify against your utility's transformer impedance and cable length.

Built-in release and auxiliary switch complement

No ground-fault monitoring is included on this version.

Depth of 86 mm includes the body but not handle projection; allow clearance for the UVR wiring and communication cable bend radius in the enclosure layout.

Operating environment and power dissipation

The 70 °C upper operating limit matches the top of the derating curve, so the breaker can run at 70 °C but only at 200 A.

Communication and measurement capability

This breaker includes a communication function and an 'other measurement function' — likely current measurement and energy metering via a communication module (the basic switch variant is 3VA2225-5KP32-0AA0, which omits those). For a line protection MCCB, the communication allows remote trip indication, load current monitoring, and integration into a facility energy management system. No ground-fault monitoring is present on this variant.

Frequently asked questions

Does this breaker include ground-fault monitoring?

No. The ground-fault monitoring version is specified as 'Without' on this variant. If ground-fault protection is required, select a different 3VA2 variant or add an external ground-fault relay and shunt trip.

What auxiliary switches come with this variant?

It includes two HQ auxiliary switches (changeover contacts) and an undervoltage release as the auxiliary release. The HQ switches provide status feedback for open/closed position to a PLC or indicator lamp.

MPN
3VA2225-5KP32-0DC0