Its interrupting capacity reaches 187 kA at 240 V, 121 kA at 415 V, and 121 kA at 440 V — meaning it can safely clear high-fault currents in low-voltage mains without upstream cascading. At 690 V the rating drops to 4.5 kA, so this breaker is best suited for 400 V-class systems where the full 121 kA is available. Thermal derating starts at 55 °C: 238 A at 55 °C, 225 A at 60 °C, 213 A at 65 °C, and 200 A at 70 °C.
Integration notes
No auxiliary switch or undervoltage release is fitted on this variant.