Skip to main content
Siemens 3VA2225-6HL32-0JA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2225-6HL32-0JA0 SENTRON MCCB, 250 A, 242 kA at 24

MPN3VA2225-6HL32-0JA0

Siemens SENTRON 3VA series molded case circuit breaker, 3VA2225-6HL32-0JA0, 250 A rated, 3-pole, line protection, ETU320 overcurrent release, integrated shunt trip STL, 242 kA interrupting at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2225-6HL32-0JA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2225-6HL32-0AA0
3VA2225-6HL32-0JA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C241 A
Current at 60 °C232 A
Current at 65 °C222 A
Current at 70 °C213 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V6 kA
Power loss, max.48 W
3VA2225-6HL32-0JA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
3VA2225-6HL32-0JA0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2225-6HL32-0JA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2225-6HL32-0JA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2225-6HL32-0JA0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

Interrupting capacity is the headline here: 242 kA at 240 V, 187 kA at both 415 V and 440 V, 121 kA at 500 V, and still 6 kA at 690 V. The 250 A frame stays fully rated across the 40 °C to 50 °C ambient band; derating starts at 55 °C (241 A) and drops to 213 A by 70 °C.

Trip unit and release configuration

The shunt trip (STL) is integrated, not an add-on module, and its part number is 3VA9688-0BL32. No undervoltage release, no phase-failure detection, no ground-fault module on this variant. The base switch itself is order code 3VA2225-6HL32-0AA0. Maximum power loss is 48 W. Mechanical endurance is 20,000 operations.

Three-pole footprint, so it occupies a standard MCCB slot in a SENTRON distribution panel or any DIN-rail-mounting enclosure rated for the frame size.

Lifecycle status is current — this is an active, in-production Siemens SENTRON catalog number.

Frequently asked questions

Does the 3VA2225-6HL32-0JA0 include a shunt trip?

Yes, it has an integrated shunt trip release (STL), design code 3VA9688-0BL32. No undervoltage release or ground-fault module on this variant.

What are the physical dimensions — depth, width, height?

Depth is 86 mm, width 105 mm, height 181 mm. Three-pole footprint fits standard SENTRON panel slots.

MPN
3VA2225-6HL32-0JA0