It carries a shunt trip (STL) and two HQ auxiliary switches factory-fitted, so the internal release and signal contacts are already configured — no field add-on modules needed for basic trip indication or remote shunt control.
Breaking capacity is voltage-dependent: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 4.5 kA at 690 V. The steep drop to 4.5 kA at 690 V is typical for a 250 A frame — if your system runs 690 V, verify the available fault current stays under that limit.
Above that it derates: 241 A at 55 °C, 232 A at 60 °C, 222 A at 65 °C, and 213 A at 70 °C.