Siemens 3VA2225-6HN32-0AF0 — 250 A SENTRON MCCB with ETU350
Breaking capacity reaches 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 6 kA at 690 V — figures that govern selectivity and SCCR coordination in a distribution panel. The 250 A rating holds steady through 50 °C, then derates to 241 A at 55 °C, 232 A at 60 °C, 222 A at 65 °C, and 213 A at 70 °C.
Integration notes
Maximum power loss is 48 W, which should be factored into enclosure thermal calculations.