Siemens 3VA2225-6HN32-0AH0 SENTRON MCCB, 250 A, 242 kA

MPN3VA2225-6HN32-0AH0

Siemens SENTRON 3VA2 molded case circuit breaker, 3VA2225-6HN32-0AH0, 250 A, 3-pole, ETU350 electronic trip unit, line protection, 242 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2225-6HN32-0AH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2225-6HN32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA2225-6HN32-0AH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C241 A
Current at 60 °C232 A
Current at 65 °C222 A
Current at 70 °C213 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V6 kA
Power loss, max.48 W

Protection & Trip Unit

3VA2225-6HN32-0AH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350

Construction & Connection

3VA2225-6HN32-0AH0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2225-6HN32-0AH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA2225-6HN32-0AH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2225-6HN32-0AH0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

Siemens 3VA2225-6HN32-0AH0 — 250 A SENTRON MCCB with ETU350

The Siemens 3VA2225-6HN32-0AH0 is a 3-pole SENTRON molded case circuit breaker rated for 250 A continuous current (Iu) and fitted with an ETU350 electronic trip unit for line protection. Breaking capacity reaches 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 6 kA at 690 V — the 240 V figure covers most North American 240/277 V distribution panels, while the 415/440 V ratings handle European 400 V industrial mains. Current rating holds at 250 A from 40 °C through 50 °C ambient, then derates linearly to 213 A at 70 °C — the full thermal curve is documented, so no guesswork for high-temp enclosures.

What the ratings mean for your panel

The 242 kA SCCR at 240 V means this breaker can safely interrupt a fault current up to that level without upstream fuses needing to clear first — useful for high-capacity transformer secondaries or busway taps where available fault current runs high. Dimensions are 105 mm wide, 181 mm high, 86 mm deep. Front IP40 protection means the breaker face is protected against tools and wires >1 mm — standard for enclosed panel mounting; no gasket needed for dry indoor locations.

Lifecycle and sourcing reality

The ETU350 trip unit is the base electronic release for the 3VA2 platform — no communication module, no ground-fault monitoring, no undervoltage release on this order code. If you need those, the 3VA2 family carries plug-in accessory slots for later addition.

MPN