Its 250 A continuous current holds flat from 40 °C to 50 °C, then derates to 213 A at 70 °C — useful to know if your panel runs hot or is packed tight. An undervoltage release (UVR) is integrated as standard — the UVR coil is part of the basic switch assembly. No auxiliary contacts or communication module are fitted on this variant.
The depth of 86 mm means it clears most 200 mm deep enclosures, but check your gland-plate clearance if the panel is shallow. Maximum power loss is 50.5 W, so factor that into your thermal budget if grouping multiple breakers.