Skip to main content
Siemens 3VA2225-6HN32-0CC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2225-6HN32-0CC0 SENTRON MCCB, 250 A, 3-Pole, 242

MPN3VA2225-6HN32-0CC0

Siemens SENTRON 3VA2225-6HN32-0CC0, molded case circuit breaker, 3-pole, 250 A rated at 40 °C, 242 kA breaking capacity at 240 V, line protection design with undervoltage release and 2 auxiliary switches HQ.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2225-6HN32-0CC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2225-6HN32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA2225-6HN32-0CC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C241 A
Current at 60 °C232 A
Current at 65 °C222 A
Current at 70 °C213 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V4.5 kA
Power loss, max.50.5 W

Protection & Trip Unit

3VA2225-6HN32-0CC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2225-6HN32-0CC0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2225-6HN32-0CC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2225-6HN32-0CC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2225-6HN32-0CC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

What this MCCB delivers on the line side

The Siemens SENTRON 3VA2225-6HN32-0CC0 is a 3-pole molded case circuit breaker rated for 250 A continuous at 40 °C, designed for line protection in distribution panels. Its breaking capacity reaches 242 kA at 240 V AC, 187 kA at 415/440 V, 121 kA at 500 V, and 4.5 kA at 690 V — meaning it can safely interrupt fault currents across a wide voltage range without cascading upstream. The unit includes an undervoltage release (UVR) and two HQ auxiliary switches, so it integrates into safety circuits and remote status monitoring without an add-on module.

Sizing and thermal performance

Rated 250 A at 40, 45, and 50 °C ambient, the breaker holds full ampacity through 50 °C. Above that it derates linearly: 241 A at 55 °C, 232 A at 60 °C, 222 A at 65 °C, and 213 A at 70 °C. For a panel running warm — say a packed enclosure near a furnace line — that derating curve tells you exactly where you stand without guessing. Maximum power loss is 50.5 W, which factors into enclosure thermal calculations.

Panel fit and auxiliaries

Dimensions are 181 mm high, 105 mm wide, 86 mm deep — a standard SENTRON 3VA frame that mounts on a DIN rail or panel-mount plate. The two HQ auxiliary switches and the undervoltage release are factory-fitted, so you do not need to order them separately or open the cover. The base switch variant is 3VA2225-6HN32-0AA0; the -0CC0 suffix adds the UVR and aux switches as a configured assembly. Operating temperature range is -25 °C to +70 °C, storage from -40 °C to +80 °C.

Frequently asked questions

What is the breaking capacity of 3VA2225-6HN32-0CC0 at different voltages?

At 240 V it interrupts 242 kA; at 415 V and 440 V, 187 kA; at 500 V, 121 kA; and at 690 V, 4.5 kA. These values cover most industrial distribution voltages up to 690 V.

What auxiliaries come fitted on this MCCB?

It includes an undervoltage release (UVR) and two HQ auxiliary switches, factory-installed. The base breaker without these is order code 3VA2225-6HN32-0AA0.

Where can I buy 3VA2225-6HN32-0CC0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

MPN
3VA2225-6HN32-0CC0