Skip to main content
Siemens 3VA2225-6HN32-0KL0 — Molded Case Circuit Breakers (MCCB)

SENTRON 3VA2225-6HN32-0KL0 MCCB, 250A, 3-Pole, 242kA at 240V

MPN3VA2225-6HN32-0KL0

SENTRON 3VA2225-6HN32-0KL0, molded case circuit breaker, 3-pole, 250 A rated continuous current, 242 kA interrupting capacity at 240 V AC, line protection design with shunt trip and auxiliary switches.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2225-6HN32-0KL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2225-6HN32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22

Ratings

3VA2225-6HN32-0KL0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C241 A
Current at 60 °C232 A
Current at 65 °C222 A
Current at 70 °C213 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V4.5 kA
Power loss, max.48 W

Protection & Trip Unit

3VA2225-6HN32-0KL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2225-6HN32-0KL0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2225-6HN32-0KL0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4

Environmental

3VA2225-6HN32-0KL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2225-6HN32-0KL0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The SENTRON 3VA2225-6HN32-0KL0 is a 3-pole molded case circuit breaker rated for 250 A continuous current at 40 °C, with a maximum interrupting capacity of 242 kA at 240 V AC. Designed for line protection, it carries a shunt trip release (STL) and a full auxiliary switch complement: 2 auxiliary switches plus 1 trip alarm and 1 electrical alarm switch HQ.

Interrupting capacity and thermal derating

At 415 V and 440 V the breaker holds 187 kA, dropping to 121 kA at 500 V and 4.5 kA at 690 V — the steep roll-off above 500 V means this frame is sized for low-voltage distribution, not 690 V motor circuits. Thermal derating begins at 55 °C: 241 A at 55 °C, 232 A at 60 °C, 222 A at 65 °C, and 213 A at 70 °C. If your panel ambient runs above 50 °C, the 250 A nameplate is no longer the usable number.

Physical fit and panel integration

Dimensions: 105 mm wide, 181 mm tall, 86 mm deep. The 105 mm width is standard for a 3-pole MCCB frame in this class — verify the mounting footprint against your existing panel cutout or DIN-rail adapter. Maximum power loss is 48 W, so account for that heat in enclosure sizing if the breaker is enclosed with other high-current devices.

Environmental limits

Operating temperature range is -25 °C to 70 °C; storage range is -40 °C to 80 °C. The storage maximum exceeds the operating maximum — that limit governs handling and warehousing, not running conditions.

Frequently asked questions

How do I get current pricing and availability for 3VA2225-6HN32-0KL0?

Submit an RFQ through this listing. The part is sourced to order through independent distribution; availability and current pricing are confirmed at quote time.

What is the interrupting capacity at different voltages?

242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 4.5 kA at 690 V. The steep drop above 500 V means this breaker is sized for standard low-voltage distribution, not 690 V motor circuits.

What auxiliary switches and releases does this breaker include?

It includes a shunt trip release (STL), 2 auxiliary switches, 1 trip alarm switch, and 1 electrical alarm switch HQ. The base switch without these accessories is order code 3VA2225-6HN32-0AA0.

MPN
3VA2225-6HN32-0KL0