It is configured for line protection. Thermal derating is published across the full operating range: full 250 A up to 50 °C, then 238 A at 55 °C, 225 A at 60 °C, 213 A at 65 °C, and 200 A at 70 °C. For a panel OEM or MRO planner, that means if the breaker lives in a non-climate-controlled enclosure that hits 60 °C in summer, you must load it at 225 A or less — the rating is real, not a marketing number. Maximum power loss is 48 W, which matters for enclosure heat-budget calculations. Dimensions are 105 mm wide, 181 mm high, 86 mm deep — a 3-pole frame that fits standard SENTRON 3VA mounting patterns. Front protection is IP40, so it is splash-safe in a closed panel but not washdown-rated.

Siemens 3VA2225-6JP32-0AA0 SENTRON MCCB, 250 A, 3-Pole, ETU5
MPN3VA2225-6JP32-0AA0
Active
Siemens SENTRON 3VA2225-6JP32-0AA0, molded case circuit breaker, line protection, 3-pole, 250 A, ETU550 electronic trip unit, 242 kA at 240 V AC.
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026
Specifications
| Parameter | Value |
|---|---|
| Product designation | Molded case circuit breaker |
| Brand / range | SENTRON |
| Product version | Line protection |
| Parameter | Value |
|---|---|
| Number of poles | 3 |
| Rated operational voltage Ue (AC) | 690 V |
| Rated insulation voltage Ui | 800 V |
| Current at 40 °C | 250 A |
| Current at 45 °C | 250 A |
| Current at 50 °C | 250 A |
| Current at 55 °C | 238 A |
| Current at 60 °C | 225 A |
| Current at 65 °C | 213 A |
| Current at 70 °C | 200 A |
| Switching capacity class | H |
| Breaking capacity at 240 V | 242 kA |
| Breaking capacity at 415 V | 187 kA |
| Breaking capacity at 440 V | 187 kA |
| Breaking capacity at 500 V | 121 kA |
| Breaking capacity at 690 V | 4.5 kA |
| Power loss, max. | 48 W |
| Parameter | Value |
|---|---|
| Overcurrent release (trip unit) type | ETU550 |
| Overcurrent protection function | LSI |
| Ground-fault monitoring | Without |
| Parameter | Value |
|---|---|
| Main circuit connection type | on both sides nut keeper kit |
| Main circuit connector arrangement | Front terminal |
| Protection class (IP), front | IP40 |
| Parameter | Value |
|---|---|
| Undervoltage release | No |
| Voltage trigger | No |
| Trip indicator | No |
| Communication function | Yes |
| Measurement function | No |
| Motor drive option | Yes |
| Auxiliary CO contacts | 0 |
| Parameter | Value |
|---|---|
| Operating temperature, max. | 70 °C |
| Operating temperature, min. | -25 °C |
| Storage temperature, max. | 80 °C |
| Storage temperature, min. | -40 °C |
| Parameter | Value |
|---|---|
| Height | 181 mm |
| Width | 105 mm |
| Depth | 86 mm |
| Height (in) | 7.13 in |
| Width (in) | 4.13 in |
| Depth (in) | 3.39 in |
Product details
MPN
3VA2225-6JP32-0AA0