Skip to main content
Siemens 3VA2225-6JP32-0AC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2225-6JP32-0AC0 SENTRON MCCB, 250 A, 3-Pole, 242

MPN3VA2225-6JP32-0AC0

Siemens SENTRON molded case circuit breaker, 3VA2225-6JP32-0AC0, 3-pole, 250 A, 242 kA at 240 V, line protection with communication function.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2225-6JP32-0AC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2225-6JP32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA2225-6JP32-0AC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C238 A
Current at 60 °C225 A
Current at 65 °C213 A
Current at 70 °C200 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V4.5 kA
Power loss, max.48 W

Protection & Trip Unit

3VA2225-6JP32-0AC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2225-6JP32-0AC0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2225-6JP32-0AC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2225-6JP32-0AC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2225-6JP32-0AC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

What this MCCB carries

The Siemens SENTRON 3VA2225-6JP32-0AC0 is a 3-pole molded case circuit breaker rated for 250 A continuous current at 40 °C, with a breaking capacity of 242 kA at 240 V AC — that's the short-circuit withstand you'd spec for a high-fault service entrance or a large motor control center fed close to the transformer. At 415 V and 440 V it still holds 187 kA, dropping to 121 kA at 500 V and 4.5 kA at 690 V — the curve tells you this breaker is built for low-voltage high-fault applications, not 690 V distribution. Power loss maxes at 48 W, which matters for thermal management inside a sealed enclosure; the unit also includes a communication function for remote monitoring or trip indication.

Integration and mounting

Dimensions are 181 mm high, 105 mm wide, 86 mm deep — fits standard Siemens 3VA panel cutouts and busbar systems; the 3-pole footprint matches the SENTRON family, so a swap from a lower-rated 3VA frame keeps the same drill plan. Comes with two HQ auxiliary switches built in (no separate add-on needed for status feedback), and no undervoltage release or ground-fault module — those are options you add externally if the application demands them.

Thermal derating and operating range

Rated 250 A up to 50 °C ambient; above that it derates stepwise — 238 A at 55 °C, 225 A at 60 °C, 213 A at 65 °C, and 200 A at 70 °C. If your panel runs hot, that's the real continuous current you can count on. Operating temperature range is -25 °C to +70 °C; storage from -40 °C to +80 °C — fine for unheated warehouses or outdoor cabinets in temperate climates.

Frequently asked questions

Where can I buy 3VA2225-6JP32-0AC0 and how do I get a price?

We source this part to order against an RFQ through our independent distribution network. Submit a request for current pricing and lead time — availability is confirmed at quote time.

What is 3VA2225-6JP32-0AC0's listed depth and width?

Depth is 86 mm and width is 105 mm, with a height of 181 mm — standard 3VA frame dimensions.

Will 3VA2225-6JP32-0AC0 drop into a panel specified around 3VA1110-5ED36-0AC0 without rewiring?

Both are 3-pole SENTRON MCCBs on the same 3VA frame, so the mounting footprint and busbar spacing are identical. The 3VA2225 carries a higher continuous rating (250 A vs the 3VA1110's lower rating) — verify the cable and busbar ampacity before swapping up.

MPN
3VA2225-6JP32-0AC0