Skip to main content
Siemens 3VA2225-6JP32-0CC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2225-6JP32-0CC0 SENTRON MCCB, 250 A, 3-Pole, ETU5

MPN3VA2225-6JP32-0CC0

Siemens SENTRON 3VA2225-6JP32-0CC0, molded case circuit breaker, 3-pole, 250 A rated continuous current, ETU550 electronic trip unit, line protection, breaking capacity 242 kA at 240 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2225-6JP32-0CC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2225-6JP32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA2225-6JP32-0CC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C238 A
Current at 60 °C225 A
Current at 65 °C213 A
Current at 70 °C200 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V6 kA
Power loss, max.50.5 W
3VA2225-6JP32-0CC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550
3VA2225-6JP32-0CC0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2225-6JP32-0CC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA2225-6JP32-0CC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2225-6JP32-0CC0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

It's part of the 3VA series, which replaced the older 3VL line and sits as the current-generation platform for panelboard and switchboard feeder protection. Breaking capacity hits 242 kA at 240 V AC, 187 kA at 415 V, and 121 kA at 500 V — numbers that put it in the high-interrupting category for industrial distribution.

Trip unit and auxiliaries

The ETU550 is a microprocessor-based electronic trip unit offering LSIG protection (long-time, short-time, instantaneous, ground-fault) with adjustable settings. Communication function is built in — this variant supports fieldbus integration for power monitoring and remote trip indication, which saves adding a separate metering module. The base switch mechanism is 3VA2225-6JP32-0AA0. No voltage trigger or phase failure detection on this variant.

Full 250 A rating holds up to 50 °C ambient. Above that it derates linearly: 238 A at 55 °C, 225 A at 60 °C, 213 A at 65 °C, and 200 A at 70 °C.

Frequently asked questions

What trip unit is on the 3VA2225-6JP32-0CC0?

An ETU550 electronic trip unit with LSIG protection — long-time, short-time, instantaneous, and ground-fault — all field-adjustable. It also includes a communication function for remote monitoring and trip indication.

MPN
3VA2225-6JP32-0CC0