Skip to main content
Siemens 3VA2225-6JP32-0CC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2225-6JP32-0CC0 SENTRON MCCB, 250 A, 3-Pole, ETU5

MPN3VA2225-6JP32-0CC0

Siemens SENTRON 3VA2225-6JP32-0CC0, molded case circuit breaker, 3-pole, 250 A rated continuous current, ETU550 electronic trip unit, line protection, breaking capacity 242 kA at 240 V AC.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2225-6JP32-0CC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2225-6JP32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA2225-6JP32-0CC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C238 A
Current at 60 °C225 A
Current at 65 °C213 A
Current at 70 °C200 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V6 kA
Power loss, max.50.5 W

Protection & Trip Unit

3VA2225-6JP32-0CC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550

Construction & Connection

3VA2225-6JP32-0CC0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2225-6JP32-0CC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2225-6JP32-0CC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2225-6JP32-0CC0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

What this MCCB carries

The Siemens SENTRON 3VA2225-6JP32-0CC0 is a 3-pole molded case circuit breaker (MCCB) rated for 250 A continuous current (Iu) with an ETU550 electronic trip unit, configured for line protection duty. It's part of the 3VA series, which replaced the older 3VL line and sits as the current-generation platform for panelboard and switchboard feeder protection. Breaking capacity hits 242 kA at 240 V AC, 187 kA at 415 V, and 121 kA at 500 V — numbers that put it in the high-interrupting category for industrial distribution. At 690 V it still holds 6 kA, enough for most motor-circuit coordination studies.

Trip unit and auxiliaries

The ETU550 is a microprocessor-based electronic trip unit offering LSIG protection (long-time, short-time, instantaneous, ground-fault) with adjustable settings. Communication function is built in — this variant supports fieldbus integration for power monitoring and remote trip indication, which saves adding a separate metering module. It ships with an undervoltage release (UVR) installed (order code 3VA9608-0BB24) and 2 high-capacity auxiliary switches (HQ type). The base switch mechanism is 3VA2225-6JP32-0AA0. No voltage trigger or phase failure detection on this variant.

Thermal derating and panel fit

Full 250 A rating holds up to 50 °C ambient. Above that it derates linearly: 238 A at 55 °C, 225 A at 60 °C, 213 A at 65 °C, and 200 A at 70 °C. If the panel ambient runs hot, factor that into the feeder schedule — don't just read the nameplate. Dimensions are 181 mm high × 105 mm wide × 86 mm deep. The 105 mm width is standard for a 250 A frame in the 3VA range.

Frequently asked questions

What trip unit is on the 3VA2225-6JP32-0CC0?

An ETU550 electronic trip unit with LSIG protection — long-time, short-time, instantaneous, and ground-fault — all field-adjustable. It also includes a communication function for remote monitoring and trip indication.

MPN
3VA2225-6JP32-0CC0