Siemens 3VA2225-6JP32-0KL0 SENTRON MCCB, 250 A, 242 kA

MPN3VA2225-6JP32-0KL0

Siemens SENTRON 3VA2 series, Molded case circuit breaker (MCCB), 3VA2225-6JP32-0KL0, 250 A rated continuous current Iu, 242 kA breaking capacity at 240 V, 3-pole, ETU550 electronic trip unit, shunt trip STL, current-production.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2225-6JP32-0KL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2225-6JP32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22

Ratings

3VA2225-6JP32-0KL0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C238 A
Current at 60 °C225 A
Current at 65 °C213 A
Current at 70 °C200 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V6 kA
Power loss, max.48 W

Protection & Trip Unit

3VA2225-6JP32-0KL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550

Construction & Connection

3VA2225-6JP32-0KL0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2225-6JP32-0KL0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4

Environmental

3VA2225-6JP32-0KL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2225-6JP32-0KL0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

Line protection MCCB with ETU550 and comms

The Siemens SENTRON 3VA2225-6JP32-0KL0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection, carrying a continuous current Iu of 250 A and a rated insulation voltage Ui of 800 V. The 242 kA breaking capacity at 240 V means it can safely interrupt very high fault currents on the secondary side of a distribution transformer — typical for a main incoming breaker in a large industrial panel. The ETU550 electronic trip unit gives you adjustable long-time, short-time, instantaneous, and ground-fault protection curves, plus communication capability for integration into a power monitoring system.

Breaking capacity across voltages — what the numbers mean

This MCCB delivers 242 kA at 240 V, 187 kA at both 415 V and 440 V, 121 kA at 500 V, and 6 kA at 690 V. The steep drop at 690 V reflects the physical limits of the arc-extinction system at higher voltages — if your system runs 690 V, the available fault current must stay under 6 kA, which typically means a transformer-impedance-limited installation or a downstream breaker. For 400 V class panels (common in European industrial mains), the 187 kA rating covers virtually any installation without an upstream current-limiting fuse.

Temperature derating — the real current you can carry

The breaker carries its full 250 A from 40 °C through 50 °C. At 55 °C it derates to 238 A, at 60 °C to 225 A, at 65 °C to 213 A, and at 70 °C to 200 A. If the panel ambient runs hot — say near a row of drives or inside a non-ventilated enclosure — the 70 °C figure of 200 A is the one to size your load against. The maximum operating temperature is 70 °C; storage range is -40 °C to 80 °C.

Auxiliary contacts and releases

Factory-fitted with 2 auxiliary switches plus 1 trip alarm switch plus 1 electrical alarm switch (HQ configuration). The shunt trip release (STL) is included for remote tripping — useful for emergency-stop circuits or supervisory shutdown. The undervoltage release is not present on this variant. The basic switch assembly carries order code 3VA2225-6JP32-0AA0; the integrated auxiliary trip is 3VA9688-0BL33.

Physical fit — panel cutout and mounting

Dimensions: 105 mm wide, 181 mm tall, 86 mm deep. This is a standard 3-pole SENTRON 3VA2 frame size — mounts via four screws to a backplate or DIN-rail adapter. The 86 mm depth leaves clearance for rear-access wiring in a 200 mm deep enclosure. Power loss is 48 W maximum at rated current, so factor that into the enclosure thermal budget.

Frequently asked questions

How do I get current pricing and availability for 3VA2225-6JP32-0KL0?

Submit an RFQ through the storefront. This part is sourced to order through independent distribution; pricing and stock are confirmed at quote time.

What is the breaking capacity of this MCCB at 415 V?

187 kA at 415 V, which covers virtually any 400 V class industrial main without an upstream current-limiting fuse.

What is the depth of 3VA2225-6JP32-0KL0?

86 mm deep, which leaves clearance for rear-access wiring in a 200 mm deep enclosure.

What trip unit is fitted on this breaker?

The ETU550 electronic trip unit, offering adjustable long-time, short-time, instantaneous, and ground-fault protection curves with communication capability.

What auxiliary contacts does this variant include?

2 auxiliary switches plus 1 trip alarm switch plus 1 electrical alarm switch (HQ configuration), plus a shunt trip release (STL) for remote tripping.

MPN