Skip to main content
Siemens 3VA2225-6KQ32-0KA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2225-6KQ32-0KA0 SENTRON MCCB, 250 A, 3-Pole, 242

MPN3VA2225-6KQ32-0KA0

Siemens SENTRON 3VA2225-6KQ32-0KA0, molded case circuit breaker, 3-pole, 250 A rated, 242 kA breaking at 240 V AC, shunt trip release, communication capable.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2225-6KQ32-0KA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.#BEZUG!

Ratings

3VA2225-6KQ32-0KA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C238 A
Current at 60 °C225 A
Current at 65 °C213 A
Current at 70 °C200 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V4.5 kA
Power loss, max.48 W

Protection & Trip Unit

3VA2225-6KQ32-0KA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU860
Overcurrent protection functionLSIG
Ground-fault monitoringSummation current formation L-conductor
Grounding protection functionYes

Construction & Connection

3VA2225-6KQ32-0KA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2225-6KQ32-0KA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2225-6KQ32-0KA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2225-6KQ32-0KA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The Siemens SENTRON 3VA2225-6KQ32-0KA0 is a 3-pole molded case circuit breaker (MCCB) rated for 250 A continuous at 40 °C, with a full-scale setting range from 50 A to 250 A. Its headline breaking capacity hits 242 kA at 240 V AC — that's the fault current it can safely interrupt without welding contacts or rupturing the case, which means it handles high-fault utility feeds or transformer secondaries where upstream coordination demands a robust interrupt rating.

Breaking capacity across voltages — what the numbers mean for your panel

This MCCB delivers 242 kA at 240 V, 187 kA at both 415 V and 440 V, 121 kA at 500 V, and 4.5 kA at 690 V. The steep drop at 690 V tells you the internal arc-extinction design is optimized for the 400–500 V range typical of industrial distribution. If your system runs 690 V, verify the available fault current stays under 4.5 kA — otherwise you need a current-limiting upstream device or a higher-rated frame.

Thermal derating — the real-world current you can count on

Rated 250 A at 40 °C, 45 °C, and 50 °C without derating. Above that: 238 A at 55 °C, 225 A at 60 °C, 213 A at 65 °C, and 200 A at 70 °C. For a panel that sees 55 °C ambient (common in sealed enclosures or near heat sources), you lose 12 A — plan your load margin accordingly. The operating temperature range is -25 °C to 70 °C; storage range is -40 °C to 80 °C.

Mounting and integration — panel fit and connections

Dimensions are 181 mm height, 105 mm width, 86 mm depth. It's a standard MCCB footprint for a 3-pole frame at this rating — mounts on a DIN rail or directly to a backplate via the base slots. The shunt trip release (STL) is built in, so you can wire a remote trip from an E-stop or safety relay without adding an external module. Communication function is present on this variant, meaning it can report status or accept remote commands over a bus — check the specific protocol (PROFIBUS, PROFINET, or Modbus) against your control network.

Frequently asked questions

Where can I buy 3VA2225-6KQ32-0KA0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — send your target quantity and delivery window.

What is the breaking capacity of 3VA2225-6KQ32-0KA0 at 415 V?

At 415 V AC, the breaking capacity is 187 kA. The same rating applies at 440 V.

Does 3VA2225-6KQ32-0KA0 include a shunt trip?

Yes, the auxiliary release design is a shunt trip (STL), enabling remote tripping from safety circuits or emergency stops.

MPN
3VA2225-6KQ32-0KA0