Skip to main content
Siemens 3VA2225-7HL32-0BA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2225-7HL32-0BA0 SENTRON MCCB, 250 A, 3-pole, ETU3

MPN3VA2225-7HL32-0BA0

Siemens SENTRON 3VA2225-7HL32-0BA0, molded case circuit breaker, 3-pole, 250 A, ETU320 electronic trip unit, line protection, 330 kA at 240 V, 242 kA at 415 V, 86 mm depth, 105 mm width, 181 mm height.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2225-7HL32-0BA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2225-7HL32-0AA0

Ratings

3VA2225-7HL32-0BA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C241 A
Current at 60 °C232 A
Current at 65 °C222 A
Current at 70 °C213 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V6.3 kA
Power loss, max.50.5 W

Protection & Trip Unit

3VA2225-7HL32-0BA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320

Construction & Connection

3VA2225-7HL32-0BA0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2225-7HL32-0BA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2225-7HL32-0BA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2225-7HL32-0BA0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

Siemens SENTRON 3VA2225-7HL32-0BA0 — 250 A MCCB with ETU320

The Siemens SENTRON 3VA2225-7HL32-0BA0 is a 3-pole molded case circuit breaker rated for 250 A continuous current at 40 °C, using an ETU320 electronic trip unit for line protection. Its interrupting capacity reaches 330 kA at 240 V and 242 kA at 415 V, dropping to 6.3 kA at 690 V — the high fault-current headroom at low voltages makes it a fit for transformer secondary or bus-tie applications where available fault current is extreme.

What the ratings mean for your panel

The 250 A rating holds flat from 40 °C to 50 °C, then derates to 241 A at 55 °C, 232 A at 60 °C, 222 A at 65 °C, and 213 A at 70 °C. If your enclosure ambient runs above 50 °C, size the breaker for the derated value — not the nameplate 250 A. The 800 V rated insulation voltage (Ui) covers 480 V and 600 V class systems with margin. The ETU320 electronic trip unit provides adjustable long-time, short-time, instantaneous, and ground-fault protection (though this variant ships without ground-fault monitoring). No communication module, no phase-failure detection, and no auxiliary contacts are included — this is a bare line-protection breaker. An undervoltage release (UVR) is fitted as standard.

Frequently asked questions

Does this breaker include an undervoltage release?

Yes, an undervoltage release (UVR) is fitted as standard. The integrated auxiliary trip is order code 3VA9608-0BB11.

MPN
3VA2225-7HL32-0BA0