Skip to main content
Siemens 3VA2225-7HL32-0JH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2225-7HL32-0JH0 SENTRON MCCB, 250 A, 3-Pole, 330

MPN3VA2225-7HL32-0JH0

Siemens SENTRON 3VA2225-7HL32-0JH0, molded case circuit breaker, 3-pole, 250 A continuous, line protection, 330 kA breaking capacity at 240 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2225-7HL32-0JH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2225-7HL32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA2225-7HL32-0JH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C241 A
Current at 60 °C232 A
Current at 65 °C222 A
Current at 70 °C213 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V4.5 kA
Power loss, max.48 W
3VA2225-7HL32-0JH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2225-7HL32-0JH0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2225-7HL32-0JH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA2225-7HL32-0JH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2225-7HL32-0JH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

Its interrupting capacity reaches 330 kA at 240 V AC, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 4.5 kA at 690 V — figures that define the available fault current it can safely clear without upstream cascading.

The 250 A rating holds flat from 40 °C through 50 °C ambient, then derates to 241 A at 55 °C, 232 A at 60 °C, 222 A at 65 °C, and 213 A at 70 °C. For a panel OEM or MRO planner slotting this into an existing enclosure, the dimensions are 105 mm wide, 181 mm high, and 86 mm deep — a 3-pole footprint that drops into a standard SENTRON 3VA mounting base without rewiring from the 3VA2116-5JP32-0AE0 or other 3VA frame siblings, provided the busbar and lug kit match the 250 A continuous rating.

Frequently asked questions

Will 3VA2225-7HL32-0JH0 drop into a panel specified around 3VA2116-5JP32-0AE0 without rewiring?

Yes — both are 3-pole SENTRON 3VA frame MCCBs sharing the same 105 mm width, 181 mm height, and 86 mm depth, so the mechanical footprint and mounting base are identical. The busbar and lug kit must be rated for 250 A continuous on this variant versus the lower rating of the 3VA2116-5JP32-0AE0.

What auxiliary switches and releases are fitted?

This variant includes 2 auxiliary switches plus 1 trip alarm switch (HQ design) and a shunt trip release (STL) for remote opening. There is no undervoltage release and no ground-fault monitoring module.

MPN