Its interrupting capacity reaches 330 kA at 240 V and 242 kA at 415 V and 440 V, dropping to 4.5 kA at 690 V — so the fault-current rating you need to match is the one at your system voltage, not the headline number. No undervoltage release is fitted, and there is no communication module onboard.
Thermal derating and trip settings
Above that it derates: 241 A at 55 °C, 232 A at 60 °C, 222 A at 65 °C, and 213 A at 70 °C. The adjustable thermal-magnetic trip has a full-scale value of 250 A and an initial value of 50 A, giving a 5:1 adjustment range for coordinating with downstream feeders. A trip indicator is present for quick fault identification during troubleshooting.
Maximum power loss is 48 W, so ventilation around the breaker in a sealed enclosure should be checked.