Skip to main content
Siemens 3VA2225-7HN32-0DC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2225-7HN32-0DC0 SENTRON MCCB, 250 A, 3-Pole, 330

MPN3VA2225-7HN32-0DC0

Siemens SENTRON 3VA2225-7HN32-0DC0, molded case circuit breaker, 3-pole, 250 A continuous, 330 kA at 240 VAC, line protection design with undervoltage release and 2 HQ auxiliary switches.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2225-7HN32-0DC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2225-7HN32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA2225-7HN32-0DC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C241 A
Current at 60 °C232 A
Current at 65 °C222 A
Current at 70 °C213 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V4.5 kA
Power loss, max.50.5 W

Protection & Trip Unit

3VA2225-7HN32-0DC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2225-7HN32-0DC0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2225-7HN32-0DC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2225-7HN32-0DC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2225-7HN32-0DC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

What this MCCB carries and where it fits

The Siemens SENTRON 3VA2225-7HN32-0DC0 is a 3-pole molded case circuit breaker rated for 250 A continuous current, sized for line protection in distribution panels. Its interrupting capacity hits 330 kA at 240 VAC and stays at 242 kA through 440 VAC, then drops to 187 kA at 500 VAC and 4.5 kA at 690 VAC — so the voltage class of your service entrance or feeder panel decides which rating governs the fault duty. The breaker carries an undervoltage release (UVR) and two HQ auxiliary switches, meaning it can trip on loss of control voltage and report position back to a PLC or status lamp without an add-on module. That UVR is a common spec for safety circuits where a drop in control power must open the main breaker. Thermal derating starts at 55 °C: the breaker holds 250 A flat through 50 °C, then steps down to 241 A at 55 °C, 232 A at 60 °C, 222 A at 65 °C, and 213 A at 70 °C. If your panel ambient runs above 50 °C, size the load or the breaker accordingly — the continuous rating at 70 °C is 213 A, not 250 A. Maximum power loss is 50.5 W, which matters for enclosure heat rise calculations in a sealed panel. Physical footprint: 105 mm wide, 181 mm tall, 86 mm deep. That 105 mm width is the standard 3-pole MCCB form factor for this class — it fits the same panel cutout and busbar spacing as other SENTRON 3VA2 frame breakers. Operating temperature range is -25 °C to 70 °C; storage range is -40 °C to 80 °C.

What the auxiliary release and switches add

The built-in undervoltage release (UVR) trips the breaker when control voltage drops below its dropout threshold — typical for emergency-stop chains or undervoltage protection schemes where a loss of control power must open the main circuit. The two HQ auxiliary switches provide electrically isolated position feedback (open/closed) for PLC inputs or status indicators. Because both are factory-integrated into the 3VA2225-7HN32-0DC0 variant, there is no separate kit to order or install; the breaker arrives ready for control wiring to the UVR coil and the auxiliary terminals.

Frequently asked questions

Where can I buy 3VA2225-7HN32-0DC0 and how do I get a price?

This part is sourced to order through independent distribution. Submit an RFQ against this order code for current pricing and availability — both are confirmed at quote time.

What is the continuous current rating of 3VA2225-7HN32-0DC0 at elevated ambient temperatures?

The breaker is rated 250 A continuous from 40 °C to 50 °C. Above 50 °C it derates: 241 A at 55 °C, 232 A at 60 °C, 222 A at 65 °C, and 213 A at 70 °C. Use the 70 °C figure for sealed panel sizing.

What interrupting capacity does 3VA2225-7HN32-0DC0 deliver at 480 VAC?

The interrupting capacity is 242 kA at 440 VAC and 187 kA at 500 VAC. At 480 VAC (common in North American 480Y/277 V systems) the rating falls between those two points — conservatively use the 187 kA figure at 500 VAC for coordination studies unless the manufacturer publishes a specific 480 V value.

Does 3VA2225-7HN32-0DC0 include an undervoltage release?

Yes, it is factory-equipped with an undervoltage release (UVR) that trips the breaker on loss of control voltage. It also includes two HQ auxiliary switches for position feedback.

MPN