It carries a shunt trip release (STL) for remote tripping, and its interrupting capacity reaches 330 kA at 240 V, 242 kA at 415/440 V, 187 kA at 500 V, and 4.5 kA at 690 V — the high-end figures at 240–500 V make it a strong candidate for high-fault service-entrance or feeder duty where SCCR headroom is critical.
Above 50 °C it steps down linearly: 241 A at 55 °C, 232 A at 60 °C, 222 A at 65 °C, and 213 A at 70 °C. Maximum power loss is 48 W. The 105 mm width, 181 mm height, and 86 mm depth fit standard panel-mount cutouts for this frame class — verify the existing panel's mounting footprint if retrofitting.