Skip to main content
Siemens 3VA2225-8HL32-0BL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2225-8HL32-0BL0 SENTRON MCCB, 250 A, 3-Pole, 86 m

MPN3VA2225-8HL32-0BL0

Siemens SENTRON 3VA2225-8HL32-0BL0 molded case circuit breaker, 250 A continuous, 3-pole, line protection, 440 kA breaking capacity at 240 V, 86 x 105 x 181 mm.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2225-8HL32-0BL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2225-8HL32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22

Ratings

3VA2225-8HL32-0BL0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C241 A
Current at 60 °C232 A
Current at 65 °C222 A
Current at 70 °C213 A
Switching capacity classL
Breaking capacity at 240 V440 kA
Breaking capacity at 415 V330 kA
Breaking capacity at 440 V330 kA
Breaking capacity at 500 V220 kA
Breaking capacity at 690 V52.5 kA
Power loss, max.50.5 W

Protection & Trip Unit

3VA2225-8HL32-0BL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2225-8HL32-0BL0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2225-8HL32-0BL0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4

Environmental

3VA2225-8HL32-0BL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2225-8HL32-0BL0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

Siemens 3VA2225-8HL32-0BL0 — 250 A SENTRON MCCB for Line Protection

The Siemens 3VA2225-8HL32-0BL0 is a SENTRON molded case circuit breaker (MCCB) rated for 250 A continuous current at 40 °C, designed for line protection in industrial power distribution. Its 3-pole construction and 86 mm depth fit standard panel layouts, with a width of 105 mm and height of 181 mm. Breaking capacity is 440 kA at 240 V, 330 kA at 415 V and 440 V, 220 kA at 500 V, and 52.5 kA at 690 V — covering high-fault installations across common voltage levels. Thermal derating is minimal up to 50 °C (still 250 A), then drops to 241 A at 55 °C, 232 A at 60 °C, 222 A at 65 °C, and 213 A at 70 °C. The undervoltage release (UVR) is built in, and the auxiliary switch complement includes 2 auxiliary switches, 1 trip alarm switch, and 1 electrical alarm switch (HQ type).

Mounting and Integration

At 86 mm deep, 105 mm wide, and 181 mm tall, the 3VA2225-8HL32-0BL0 fits standard panel cutouts for 3-pole MCCBs. The supplied basic switch is order code 3VA2225-8HL32-0AA0. Maximum power loss is 50.5 W, which should be factored into enclosure thermal calculations.

Frequently asked questions

What is the breaking capacity of 3VA2225-8HL32-0BL0 at 415 V?

Breaking capacity is 330 kA at 415 V, and the same at 440 V. At 240 V it reaches 440 kA, at 500 V it is 220 kA, and at 690 V it is 52.5 kA.

Where can I buy 3VA2225-8HL32-0BL0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
3VA2225-8HL32-0BL0