Skip to main content
Siemens 3VA2225-8HL32-0CL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2225-8HL32-0CL0 SENTRON MCCB, 250 A, 440 kA at 24

MPN3VA2225-8HL32-0CL0

Siemens SENTRON 3VA2225-8HL32-0CL0, molded case circuit breaker, 3-pole, 250 A rated continuous current, ETU320 electronic trip unit, 440 kA interrupting capacity at 240 V AC, undervoltage release, line protection version.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2225-8HL32-0CL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2225-8HL32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22

Ratings

3VA2225-8HL32-0CL0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C241 A
Current at 60 °C232 A
Current at 65 °C222 A
Current at 70 °C213 A
Switching capacity classL
Breaking capacity at 240 V440 kA
Breaking capacity at 415 V330 kA
Breaking capacity at 440 V330 kA
Breaking capacity at 500 V242 kA
Breaking capacity at 690 V50.4 kA
Power loss, max.50.5 W

Protection & Trip Unit

3VA2225-8HL32-0CL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320

Construction & Connection

3VA2225-8HL32-0CL0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2225-8HL32-0CL0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4

Environmental

3VA2225-8HL32-0CL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2225-8HL32-0CL0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

250 A MCCB with 440 kA SCCR — what that means for your panel

The Siemens SENTRON 3VA2225-8HL32-0CL0 is a 3-pole molded case circuit breaker rated for 250 A continuous current (Iu) and a 440 kA interrupting capacity at 240 V AC — that SCCR figure drops to 330 kA at 415 V and 440 V, then 242 kA at 500 V, and 50.4 kA at 690 V. For a sourcing buyer, the 440 kA at 240 V means this breaker handles fault currents at the main distribution level where the utility transformer can deliver massive short-circuit energy; you need that headroom to avoid cascading failure upstream. The 250 A frame is sized for a feeder or a large motor branch circuit, and the ETU320 electronic trip unit gives you adjustable long-time, short-time, instantaneous, and ground-fault protection curves — not a fixed thermal-magnetic, so you can coordinate selectively with downstream breakers. Deployment context: this mounts in a standard switchboard or panel enclosure on a DIN rail or bolted bus connection — the 105 mm width and 181 mm height fit the SENTRON 3VA frame footprint, and the 86 mm depth leaves room for cable bending radius behind the breaker.

Derating and thermal management

The 250 A rating holds flat from 40 °C up to 50 °C ambient — no derating needed in a typical 40 °C panel. At 55 °C it drops to 241 A, at 60 °C to 232 A, at 65 °C to 222 A, and at 70 °C to 213 A. If your enclosure runs hot (say, a packed panel with multiple breakers), factor in that 213 A at 70 °C is the floor. Maximum power loss is 50.5 W — that heat has to be dissipated through the enclosure walls or forced ventilation. Operating range is -25 °C to 70 °C, storage -40 °C to 80 °C.

Auxiliary and trip accessories

This variant ships with an undervoltage release (UVR) — if control power drops, the breaker trips, which is standard for safety circuits and emergency-stop chains. The auxiliary contact block includes 2 auxiliary switches, 1 trip alarm switch, and 1 electrical alarm switch (HQ type). That gives you status feedback for PLC or SCADA: one set for breaker open/closed, one for trip condition, and one for electrical alarm. The basic switch is order code 3VA2225-8HL32-0AA0; the integrated auxiliary trip is 3VA9608-0BB24 — useful if you need to order spares or replacement sub-assemblies.

Frequently asked questions

How do I get current pricing and availability for 3VA2225-8HL32-0CL0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ and we'll respond with a firm price and delivery window.

What is the interrupting capacity at 240 V?

The 3VA2225-8HL32-0CL0 is rated for 440 kA at 240 V AC. At 415 V and 440 V it is 330 kA, at 500 V it is 242 kA, and at 690 V it is 50.4 kA.

What trip unit does this breaker use?

It uses the ETU320 electronic trip unit, which provides adjustable long-time, short-time, instantaneous, and ground-fault protection. This allows selective coordination with downstream breakers.

Does this MCCB include an undervoltage release?

Yes, it is equipped with an undervoltage release (UVR) that trips the breaker when control power drops below the dropout threshold — standard for safety circuits and emergency-stop applications.

MPN
3VA2225-8HL32-0CL0