Siemens 3VA2225-8KQ32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2225-8KQ32-0AA0 SENTRON MCCB, 250A, 3-Pole, 440kA

MPN3VA2225-8KQ32-0AA0
Active

Siemens SENTRON 3VA2225-8KQ32-0AA0, molded case circuit breaker, 3-pole, 250 A continuous, line protection, with communication function.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2225-8KQ32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA2225-8KQ32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C238 A
Current at 60 °C225 A
Current at 65 °C213 A
Current at 70 °C200 A
Switching capacity classL
Breaking capacity at 240 V440 kA
Breaking capacity at 415 V330 kA
Breaking capacity at 440 V330 kA
Breaking capacity at 500 V220 kA
Breaking capacity at 690 V52.5 kA
Power loss, max.48 W

Protection & Trip Unit

3VA2225-8KQ32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU860
Overcurrent protection functionLSIG
Ground-fault monitoringSummation current formation L-conductor
Grounding protection functionYes

Construction & Connection

3VA2225-8KQ32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2225-8KQ32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2225-8KQ32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2225-8KQ32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

Siemens SENTRON 3VA2225-8KQ32-0AA0 — 250 A MCCB with Communication

The Siemens SENTRON 3VA2225-8KQ32-0AA0 is a 3-pole molded case circuit breaker (MCCB) rated for 250 A continuous current at 40 °C, designed for line protection in distribution panels. It carries a breaking capacity of 440 kA at 240 VAC and 330 kA at 415 VAC, so it handles high-fault scenarios typical in industrial mains or sub-distribution boards without cascading upstream. The built-in communication function and ground-fault monitoring via summation current formation mean this breaker can report status and fault data to a BMS or PLC — a key differentiator from a standard thermal-magnetic MCCB.

Thermal Derating and Real-World Current Capacity

The 250 A rating holds from 40 °C to 50 °C. Above that, it derates linearly: 238 A at 55 °C, 225 A at 60 °C, 213 A at 65 °C, and 200 A at 70 °C (–). For a panel with ambient near 60 °C — say, a packed enclosure next to a furnace line — the effective continuous current drops to 225 A. The 48 W maximum power loss is the heat the breaker dumps into the enclosure; factor that into the thermal budget.

Breaking Capacity Across Voltage Tiers

The interrupting ratings span the voltage range: 440 kA at 240 V, 330 kA at 415 V and 440 V, 220 kA at 500 V, and 52.5 kA at 690 V (–). At 690 V the breaker still clears 52.5 kA — enough for most 690 V industrial drives or mining distribution. The insulation voltage is rated 800 V, so the breaker is electrically safe for 690 V line-to-line systems.

Trip Unit and Adjustability

Trip unit minimum setting is 375 A, maximum is 2,500 A, full-scale value is 250 A.

Physical Fit and Mounting

Dimensions: 181 mm height, 105 mm width, 86 mm depth.

Environmental and Operating Range

Operates from -25 °C to 70 °C. Storage range is -40 °C to 80 °C — that wider storage window governs handling and warehousing, not running conditions. The breaker is designed for line protection, meaning it protects cables and busbars against overload and short circuit, not motor or generator protection.

Frequently asked questions

Does 3VA2225-8KQ32-0AA0 have communication capability?

Yes, it includes a communication function and a ground-fault monitoring function with summation current formation on the line conductor.

MPN
3VA2225-8KQ32-0AA0