Siemens 3VA2325-0HM42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2325-0HM42-0AA0 SENTRON MCCB, 250 A, 4-Pole, ETU3

MPN3VA2325-0HM42-0AA0
Active

Siemens SENTRON 3VA2325-0HM42-0AA0, molded case circuit breaker, 4-pole, 250 A continuous, ETU330 electronic trip unit, 440 kA breaking capacity at 415 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2325-0HM42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2325-0HM42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C250 A
Current at 60 °C250 A
Current at 65 °C250 A
Current at 70 °C250 A
Switching capacity classE
Breaking capacity at 415 V440 kA
Breaking capacity at 690 V187 kA
Power loss, max.37.5 W
3VA2325-0HM42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU330
Overcurrent protection functionLIG
Ground-fault monitoringSummation current formation L + N conductor
Grounding protection functionYes
3VA2325-0HM42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2325-0HM42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2325-0HM42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2325-0HM42-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width184 mm
Depth110 mm
Height (in)9.76 in
Width (in)7.24 in
Depth (in)4.33 in

Product details

The Siemens SENTRON 3VA2325-0HM42-0AA0 is a 4-pole molded case circuit breaker rated for 250 A continuous current, designed for line protection in industrial power distribution. It carries a 440 kA breaking capacity at 415 V — enough to handle high-fault-current scenarios like large transformer secondaries or busway feeds without cascading upstream. The ETU330 electronic trip unit gives adjustable overload and short-circuit protection curves, plus ground-fault monitoring via summation current formation on L+N conductors.

Ratings and what they mean for fit

The 250 A continuous rating holds flat across the full ambient range from 40 °C to 70 °C — no derating needed in a warm enclosure. That is unusual for an MCCB this size and simplifies panel thermal calculations. The 440 kA at 415 V is the short-circuit breaking capacity; it tells you this breaker can safely interrupt a fault up to that level, which is essential for high-fault installations like main switchboards or feeder breakers close to the transformer. The 187 kA at 690 V covers 600 V class systems common in North American industrial plants. Rated insulation voltage is 800 V, so the breaker is suitable for 690 V systems with margin. The 4-pole design with adjustable N-conductor protection (OFF, 50%, or 100%) makes it flexible for both solidly-grounded and impedance-grounded networks.

Panel integration and physical fit

The 3VA2325-0HM42-0AA0 measures 248 mm high, 184 mm wide, and 110 mm deep. It mounts on a DIN rail or directly to a panel backplate via the standard MCCB footprint. The front face carries IP40 protection — suitable for enclosed switchboards where tools are the only access. Spring-cage or screw terminals accept conductors sized for 250 A; verify lug kit compatibility with your busbar system.

Frequently asked questions

Where can I buy 3VA2325-0HM42-0AA0 and what is the lead time?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment.

What is the breaking capacity of 3VA2325-0HM42-0AA0?

440 kA at 415 V AC and 187 kA at 690 V AC. This is the short-circuit breaking capacity (Icu) — sufficient for main feeder or high-fault switchboard applications.

What trip unit does 3VA2325-0HM42-0AA0 use?

It uses the ETU330 electronic trip unit, which provides adjustable overload and short-circuit protection with LSI curves (long-time, short-time, instantaneous) plus ground-fault monitoring.

MPN