Skip to main content
Siemens 3VA2325-0HN32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2325-0HN32-0AA0 SENTRON MCCB, 250 A, 440 kA at 41

MPN3VA2325-0HN32-0AA0
Active

Siemens SENTRON 3VA2325-0HN32-0AA0, molded case circuit breaker, 3-pole, 250 A continuous, ETU350 electronic trip unit, 440 kA breaking capacity at 415 V AC, IP40 front protection.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2325-0HN32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2325-0HN32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C250 A
Current at 60 °C250 A
Current at 65 °C250 A
Current at 70 °C250 A
Switching capacity classE
Breaking capacity at 415 V440 kA
Breaking capacity at 690 V187 kA
Power loss, max.37.5 W
3VA2325-0HN32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2325-0HN32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2325-0HN32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2325-0HN32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2325-0HN32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

MCCB for line protection — 250 A, 440 kA at 415 V

The Siemens SENTRON 3VA2325-0HN32-0AA0 is a 3-pole molded case circuit breaker (MCCB) rated for 250 A continuous current, designed for line protection in distribution panels. Its ETU350 electronic trip unit provides adjustable overload and short-circuit protection, with a breaking capacity of 440 kA at 415 V AC — enough for high-fault installations like transformer secondaries or large motor control centers. The 690 V AC rated operating voltage and 800 V rated insulation voltage give headroom for 480 V and 600 V class systems.

The 250 A rating holds across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling, which simplifies panel thermal budgeting. The 440 kA at 415 V is the short-circuit breaking capacity (Icu) per IEC 60947-2; at 690 V it still interrupts 187 kA, covering most industrial service entrances. The ETU350 release supports LSI (long-time, short-time, instantaneous) curves, so you can coordinate downstream breakers without nuisance trips.

Dimensions are 248 mm high, 138 mm wide, 110 mm deep — fits standard MCCB panel cutouts.

Frequently asked questions

What is the breaking capacity of this MCCB?

440 kA at 415 V AC and 187 kA at 690 V AC, per IEC 60947-2. This covers high-fault installations like transformer secondaries and large motor control centers.

What trip unit does the 3VA2325-0HN32-0AA0 use?

The ETU350 electronic trip unit with LSI (long-time, short-time, instantaneous) protection curves. It allows coordination with downstream breakers.

Where can I buy 3VA2325-0HN32-0AA0?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
3VA2325-0HN32-0AA0