Skip to main content
Siemens 3VA2325-0HN42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2325-0HN42-0AA0 SENTRON MCCB, 250 A, 4-Pole, ETU3

MPN3VA2325-0HN42-0AA0
Active

Siemens SENTRON 3VA2 series, molded case circuit breaker, 3VA2325-0HN42-0AA0, 250 A rated current, 4-pole, ETU350 electronic trip unit, 440 kA breaking capacity at 415 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2325-0HN42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2325-0HN42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C250 A
Current at 60 °C250 A
Current at 65 °C250 A
Current at 70 °C250 A
Switching capacity classE
Breaking capacity at 415 V440 kA
Breaking capacity at 690 V187 kA
Power loss, max.37.5 W
3VA2325-0HN42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2325-0HN42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2325-0HN42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2325-0HN42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2325-0HN42-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width184 mm
Depth110 mm
Height (in)9.76 in
Width (in)7.24 in
Depth (in)4.33 in

Product details

The Siemens SENTRON 3VA2325-0HN42-0AA0 is a 4-pole molded case circuit breaker rated for 250 A continuous current, using the ETU350 electronic trip unit for adjustable overload and short-circuit protection. Its interrupting capacity reaches 440 kA at 415 V AC and 187 kA at 690 V AC, which means it can clear high-fault currents on the line side of a distribution panel without upstream fuses needing to open — useful for main or feeder protection in high-SCCR installations. The ETU350 release supports adjustable N-conductor protection (OFF, 50%, 100%) and is designed for line protection, not motor or generator duty — it's a distribution breaker, not a motor circuit protector.

The 250 A continuous rating holds flat from 40 °C through 70 °C ambient — no derating needed across the typical panel temperature range, which simplifies panel design for enclosures with marginal cooling. Operating ambient spans -25 °C to 70 °C; storage range is -40 °C to 80 °C, so the breaker can sit in an unheated warehouse without issue. Maximum power loss is 37.5 W — a moderate figure for a 250 A frame; plan for that heat rejection in a sealed enclosure, especially if multiple breakers are ganged.

Dimensions are 248 mm high, 184 mm wide, 110 mm deep — a standard 4-pole MCCB footprint that fits most DIN-rail or screw-mount panel layouts without modification. If you need remote trip or status feedback, look at the 3VA2 with communication option.

Frequently asked questions

What trip unit does this MCCB use?

The ETU350 electronic trip unit, which provides adjustable overload and short-circuit protection with N-conductor settings of OFF, 50%, or 100%.

MPN
3VA2325-0HN42-0AA0