It carries a continuous current rating of 250 A across the full ambient temperature range from 40 °C through 70 °C, meaning no derating is needed as the panel warms up; the breaker delivers its full 250 A at 70 °C ambient. That is unusual for an MCCB and simplifies panel design in hot enclosures or near other heat sources. Four poles handle three-phase plus neutral switching. The interrupting ratings are tiered by system voltage: 187 kA at 240 VAC, 121 kA at 415/440 VAC, 75.6 kA at 500 VAC, and 7.5 kA at 690 VAC.
Dimensions are 110 mm deep, 184 mm wide, 248 mm tall. Power loss is 37.5 W maximum at rated current.