Skip to main content
Siemens 3VA2325-5HL32-0DL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2325-5HL32-0DL0 SENTRON MCCB, 250A, 3-Pole, ETU32

MPN3VA2325-5HL32-0DL0

Siemens SENTRON, Molded case circuit breaker, 3VA2325-5HL32-0DL0, 3-pole, Line protection, 250 A, ETU320, 187 kA at 240 V, 121 kA at 415 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2325-5HL32-0DL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2325-5HL32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22
3VA2325-5HL32-0DL0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C240 A
Current at 60 °C235 A
Current at 65 °C230 A
Current at 70 °C225 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V17 kA
Power loss, max.40 W
3VA2325-5HL32-0DL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
3VA2325-5HL32-0DL0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2325-5HL32-0DL0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4
3VA2325-5HL32-0DL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2325-5HL32-0DL0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm

Product details

The 3VA2325-5HL32-0DL0: Breaking capacity is the headline: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 17 kA at 690 V. Thermal derating is published per degree: 250 A continuous through 50 °C, then 240 A at 55 °C, 235 A at 60 °C, 230 A at 65 °C, and 225 A at 70 °C.

Release and auxiliary fit

The overcurrent release is an ETU320 — a basic electronic trip unit with fixed settings, no communication function, and no phase failure detection. That UVR is the 3VA9608-0BB25 integrated auxiliary trip. The breaker includes a mechanical trip indicator and has a latching endurance of 15 000 operations — sufficient for typical distribution switching but not for frequent motor-starting duty.

Panel fit and environment

Dimensions: 138 mm wide, 248 mm high, 110 mm deep. Maximum power loss is 40 W at rated current — factor that into your enclosure thermal calculation if you are grouping several breakers in a sealed cabinet.

Frequently asked questions

What is the breaking capacity of this breaker at 415 V?

121 kA at 415 V, which is the same rating as at 440 V. At 500 V it drops to 75.6 kA, and at 690 V to 17 kA.

What overcurrent release does this MCCB use?

It uses the ETU320 electronic trip unit — a basic fixed-setting release with no communication or phase failure detection.

Where can I buy 3VA2325-5HL32-0DL0 and how is it quoted?

This breaker is sourced through independent industrial distribution channels. It is quoted to order against an RFQ; current pricing and availability are confirmed at quote time.

Will 3VA2325-5HL32-0DL0 drop into a panel specified around 3VA1112-5EF32-0CA0?

No — the 3VA1112 is a different frame size (typically 100–160 A class) with different mounting footprint and busbar spacing. The 3VA2325 is a 250 A frame; verify panel cutout and busbar centres before substituting.

MPN
3VA2325-5HL32-0DL0