Skip to main content
Siemens 3VA2325-5HL32-0HA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2325-5HL32-0HA0 SENTRON MCCB, 250 A, 3-Pole, Shun

MPN3VA2325-5HL32-0HA0

Siemens SENTRON 3VA2325-5HL32-0HA0, molded case circuit breaker, 3-pole, 250 A, line protection, with shunt trip release, breaking capacity 187 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2325-5HL32-0HA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2325-5HL32-0AA0

Ratings

3VA2325-5HL32-0HA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C250 A
Current at 60 °C250 A
Current at 65 °C250 A
Current at 70 °C250 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.37.5 W

Protection & Trip Unit

3VA2325-5HL32-0HA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2325-5HL32-0HA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2325-5HL32-0HA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2325-5HL32-0HA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2325-5HL32-0HA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

The Siemens SENTRON 3VA2325-5HL32-0HA0 is a 3-pole molded case circuit breaker rated for 250 A continuous current across the full 40 °C to 70 °C ambient range — no derating needed up to the enclosure's thermal limit. Breaking capacity reaches 187 kA at 240 V, 121 kA at 415 V/440 V, 75.6 kA at 500 V, and 7.5 kA at 690 V, so it handles high-fault utility feeds and transformer secondaries without cascading upstream. The integrated shunt trip release (STL) allows remote tripping from a safety relay or E-stop circuit, which simplifies compliance with emergency-off requirements in a single enclosure.

Physical Fit & Panel Integration

Dimensions are 248 mm high, 138 mm wide, and 110 mm deep — a standard SENTRON 3VA frame size that fits existing 3VA panel cutouts and busbar arrangements. The 3-pole block occupies a single mounting position on the DIN rail or direct-panel mount. No auxiliary switch is fitted as standard (the order code specifies "without" auxiliary switch), so if you need status feedback to a PLC or indication lamp, plan for a separate auxiliary switch block that clips onto the left side of the breaker.

Key Ratings & What They Mean for Your Panel

The 250 A continuous rating is flat from 40 °C to 70 °C — no thermal derating curve to calculate for warm enclosures. The breaking capacity at 415 V (121 kA) is the figure most relevant for European 400 V industrial networks; it ensures the breaker can interrupt a bolted fault at the main distribution board without upstream breakers needing to clear it. The shunt trip release (STL) operates on a separate control voltage — verify the coil rating matches your 24 VDC or 230 VAC control circuit (the order code does not specify the coil voltage, so confirm at ordering).

Frequently asked questions

How do I get pricing and availability for 3VA2325-5HL32-0HA0?

Submit an RFQ through this listing. We source and quote the part to order; current pricing and stock position are confirmed at quote time.

What is the breaking capacity at 415 V?

121 kA at 415 V, which is the standard industrial distribution voltage in many markets. This rating means the breaker can safely interrupt a 121 kA fault without damage.

Does this MCCB include an undervoltage release?

No, this variant has a shunt trip release (STL) for remote tripping, not an undervoltage release.

MPN
3VA2325-5HL32-0HA0