Breaking capacity is 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 7.5 kA at 690 V — numbers that matter for selectivity studies and SCCR compliance on a 480 V or 600 V line.
No communication function on board, so coordination with a BMS or PLC is via the auxiliary contacts only. Power loss maxes at 37.5 W — factor that into enclosure thermal rise calculations.
The trip indicator and voltage trigger are present; undervoltage release and ground-fault monitoring are not included on this variant.