Breaking capacity hits 187 kA at 240 V AC and 121 kA at 415/440 V AC — numbers that tell you it's built for high-fault industrial panels where selectivity and SCCR headroom matter.
This MCCB's interrupting rating drops as voltage climbs: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 17 kA at 690 V.
Thermal derating
Above that it derates: 240 A at 55 °C, 235 A at 60 °C, 230 A at 65 °C, 225 A at 70 °C.